Instruction manual
83
Boiler 
Model
Burner 
Input 
(GPH)
Burner 
Model
Nozzle
Air 
Shutter 
(setting)
Air 
Band 
(setting)
Pump 
Pressure 
(PSI)
Head 
Type 
(setting)
Insertion 
Depth 
(Inch)
Approx. 
Shipped 
CO
2
(%)
Bafe 
Location 
(pass)
Approx. 
Stack 
Temp. 
Increase 
Without 
Bafes 
°F 
(2)
Approx. 
Breech 
Pressure 
(" w.c.) 
(3)
Bafes
IN 
Approx. 
Overre 
Pressure
(" w.c.) 
(
3)
Bafes 
OUT 
Approx. 
Overre 
Pressure
(" w.c.) 
(3)
MPO-IQ84 0.60 AFG
0.50 x 45W 
Delavan
6 
(1)
0 150 L2 2 11.5 3
rd
52 0 +0.010 +0.005
MPO-IQ115 0.82 AFG
0.65 x 45B 
Delavan
6 0 150 L2 2 11.5 2
nd 
& 3
rd
84 0 +0.040 +0.020
MPO-IQ147 1.05 AFG
0.85 x 60B 
Delavan
7 1 150 L1 2 11.5 2
nd
65 0 +0.040 +0.020
MPO-IQ189 1.35 AFG
1.10 X 60B 
Hago
7 2 150 V1 (0) 2 11.5 2
nd
39 0 +0.040 +0.030
MPO-IQ231 1.65 AFG
1.35 x 60B 
Hago
7 2 150 V1 (3) 2 11.5 2
nd
18 0 +0.050 +0.030
Notes
(1)
 MPO-IQ84 at 0.60 GPH ring rate utilizes a low re bafe.
(2)
 The increased stack temperature with the bafes removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual eld conditions may 
 be different.
(3)
  These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231 could have a 
 breech pressure of -.03" w.c. and an overre pressure of .020" w.c.
4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above. Two-stage 
 fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
TABLE 16A: BECKETT AFG BURNER SPECIFICATIONS - CHIMNEY VENT
Boiler 
Model
Burner 
Input 
(GPH)
Burner 
Model
Nozzle
Air 
Gate 
(setting)
Turbulator 
(setting)
Pump 
Pressure 
(PSI)
Combustion 
Head
Insertion 
Depth 
(Inch)
Approx. 
Shipped 
CO
2
 (%)
Bafe 
Location 
(pass)
Approx. 
Stack 
Temp. 
Increase 
Without 
Bafes 
°F 
(2)
Approx. 
Breech 
Pressure 
(" w.c.) 
(3)
Bafes
IN 
Approx. 
Overre 
Pressure
(" w.c.) 
(3)
Bafes 
OUT 
Approx. 
Overre 
Pressure
(" w.c.) 
(3)
MPO-IQ84 0.60 F3
.50 x 80°W
Delavan
2.5 1.0 145 SBT 6" 2.25 11.5 3
rd
52 0 +0.010 +0.005
MPO-IQ115 0.82 F3
.65 x 70°W
Delavan
5.0 3.0 145 VSBT 2.25 11.5 2
nd 
& 3
rd
84 0 +0.040 +0.020
MPO-IQ147 1.05 F5
0.85 x 60°B 
Delavan
2.7 1.0 145 LBT 10.0" 10 11.5 2
nd
65 0 +0.040 +0.020
MPO-IQ189 1.35 F5
1.10 x 60°B 
Delavan
4.5 3.0 150 SBT 6" 3.5 11.5 2
nd
39 0 +0.040 +0.030
MPO-IQ231 1.65 F5
1.35 x 60°B 
Delavan
3.5 4.0 145 VSBT 2.25 11.5 2
nd
18 0 +0.050 +0.030
Notes
(2)
 The increased stack temperature with the bafes removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual eld conditions may be 
 different.
(3)
 These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231 could have a breech 
 pressure of -.03" w.c. and an overre pressure of .020" w.c.
4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above. Two-stage fuel 
 pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.