Operating instructions
SET  NO. 
7 
BOILER  WITH CIRCULATOR  AND  TANKLESS  DOMESTIC  HOT WATER 
IGNITION 
TRANSFORME 
IGNITION 
HONEYWELL 
R8184 
OIL 
BURNER 
OR 
HONEYWELL 
L6006A 
-0B 
I 
IMMERSION 
OPERATING 
f" 
CONTROL 
CIRCULATOR 
VALVE 
-OIL 
7P 
THERMOSTAT 
HONEYWELL 
L4080B 
IMMERSION 
LIMIT 
CONTROL 
HOT 
NEUTRAL 
ENCLOSED 
No. 
7 
Wiring Diagram for Forced Hot 
Water Boilers with Tankless Heater 
SECTION I11 
OPERATING 
and 
SERVICE INSTRUCTIONS 
Fig. 
17 
@ 
INSPECT INSTALLATION BEFORE STARTING 
d.  On  WATER  BOILERS WITHOUT  DOMESTIC 
BURNER. 
WATER  HEATERS,  set water temperature  High 
a.  WITH HOT WATER BOILER, fill entire Heating  Limit  Control at 210°F.  This  temperature may 
System  with  water and vent air from  System. 
be  varied  to suit requirements of  installation. 
b. 
WITH 
STEAM  BOILER,  fill  Boiler  to  Normal 
Water Level.  (See Figure 1). 
c. 
CHECK CONTROLS, WIRING AND BURNER to 
be  sure  that all connections  are tight and  burner 
is rigid, that  all  electrical  connections  have been 
made and fuses installed,  and  that oil  tank  is fill- 
ed and oil  lines have  been  tested. 
d. 
LUBRICATE  MOTORS  on  Oil Burner and  Circu- 
lator  (Hot  Water  Boilers),  also  bearing  on  Cir- 
culator, according  to  instructions on Circulator. 
@ 
SET CONTROLS with Burner service switch turn- 
ed  "OFF." 
a.  SET  ROOM  THERMOSTAT  about  10°F  above 
room temperature. 
b.  Press reset button  on PROTECTORELAY.. 
c.  On  STEAM  BOILERS,  set  cut-in  pressure  for 
three 
(3) 
pounds  and  differential  pressure  for 
two  (2)  pounds.  These  pressures  may  be  varied 
to  suit individual requirements of  installation. 
e.  On  WATER  BOILERS  WITH  DOMESTIC 
WATER  HEATERS,  set  Operating  Control  at 
190°F and  High  Limit Control at 210°F (at least 
20°F higher than setting of  Operating Control). 
f.  On  STEAM  BOILERS  WITH TANKLESS 
DOMESTIC WATER HEATERS, set boiler water 
temperature  Operating  Control  at 200°F. 
@ 
START OIL BURNER. Refer to  oil  burner instal- 
lation  and operation  manual  FORM  NO. 52004 for start- 
up, adjustments 
& 
servicing. 
@ 
TEST CONTROLS. 
WARNING 
- 
Before  installation  of the boiler 
is 
considered  complete,  the operation of  the boiler  controls 
should  be checked, particularly  the low water cut-off  (if 
applicable)  and the high limit control. 










