Operating instructions
@ 
INSTALLATION  OF  TRIM  AND  CONTROLS 
FOR  WATER  BOILERS.  (See Figure 
4 
for Control 
Locations.) 
a. Screw COMBINATION  ALTITUDE GAUGE  AND 
THERMOMETER  into 
%" 
tapping.  Tighten  by 
wrench applied to square shank back  of  gauge.  DO 
NOT APPLY PRESSURE ON GAUGE CASE since 
this may destroy calibration of  gauge. 
b.  RELIEF VALVE-Install  in 
1" 
Tapping next to 
3" 
Supply Tapping in Front Section using fittings pro- 
vided. 
CAUTION 
: 
Safety Relief  Valve  should  be  piped  to 
and open  drain-full  size  of  discharge  outlet  on 
Relief  Valve and without any provision of "shut-off" 
between the Relief Valve  and discharge into drain. 
c.  Install  Hydronic 
Controls  in  their  designated tap- 
pings. 
@ 
INSTALLATION  OF  TRIM  AND  CONTROLS 
FOR  STEAM BOILERS.  (See Figure 
4 
for  control 
locations.) 
a. 
Screw  Combination  Pressure  Vacuum  Gauge  into 
designated 
$" 
tapping.  Tighten by wrench applied 
to  square  shank  on  back  of  gauge.  Do  not  apply 
pressure  on  gauge case  since this may destroy cali- 
bration 
of  gauge. 
b.  SAFETY VALVE.  Install in 
1" 
Tapping next to 
3" 
Supply Tapping in Front Section. 
CAUTION:  Safety  Valve  should  be  piped  to an 
open  drain-full  size  of  discharge  outlet on Safety 
Valve  and  without  any provision of  "shut-off"  be- 
tween  the Safety Valve  and discharge  into drain. 
c.  Install Pressure  Limit  Control  with 
1/4" 
Pig  Tail 
Syphon into Heater Cover  Plate Tapping bushed 
3/4" 
to 
G". 
d.  Install  Operating  Control  (supplied with Tankless 
Heater equipped boilers only) in designated tapping. 
e. Install Gauge Glass and Low  Water Cut-off  (if  fur- 
nished)  in 
y2" 
tappings on  left side of  Front Sec- 
tion. 
@) 
INSTALL  SMOKEPIPE  so  that  connection 
to 
Chimney or vent is short and direct. 
a.  Install  in  accordance  with  LOCAL  FIRE  ORI- 
NANCES. 
b.  Smokepipe  must not be  smaller than the 
8" 
dia. flue 
collar.  See Fig. 
1. 
For Stub Vent installation  see  Fig. 
3, 
if  connected 
to chimney. 
c.  Do  not connect into same leg of  Chimney serving an 
open  fireplace. 
d.  Inspect  Chimney  for  obstructions  or  restrictions 
which  should  be  removed.  Clean Chimney if  neces- 
sary. 
e.  Smokepipe  should  slope  upward  from  Boiler  to 
Chimney not less than one inch in four feet.  Smoke- 
. 
pipe  must be  securely  supported  so as to maintain, 
proper  clearances  from  combustible  materials  and 
to prevent  separation  of  joints. 
f.  Insert Smokepipe into but not beyond  inside wall of 
Chimney  Flue  Lining.  Pipe  should  be  installed 
above the extreme bottom  of  Chimney so as  to pre- 
vent  stoppage. 
y. 
Seal between  Smokepipe and Chimney connection to 
prevent draft leakage. 
0 
INSTALL  ROOM  THERMOSTAT  on  an  inside 
wall about four feet above floor. 
Never  install Thermo- 
stat on an outside wail or where it will be  influenced by 
drafts,  hot or cold  water  pipes,  lighting  fixtures,  tele- 
vision, rays of  the sun, or near a fireplace.  Keep  large 
furniture away  from  Thermostat  so  there  will  be free 
movement  of  room air around this Control. 
@ 
OIL BURNER  INSTALLATION.  Bolt  burner  to 
mounting  plate with  nuts  and  washers packed  in  boiler 
parts  carton.  REFER  TO  BURNER  INSTALLATION 
and  SERVICE MANUAL form No. 
52004. 
I 
\ 
@) 
BOILER  with  JACKET  EXTENSION refer to 
Figure 
10 
for assembly instructions. 
h 
INSTALL ELECTRIC WIRING in accordance with 
NATIONAL ELECTRICAL  CODE  and  Local  Regula- 
tions. 
a. 
A separate ELECTRICAL CIRCUIT should be run 
from  Meter with  a  Fused  Disconnect  Switch in 
this Circuit. 
See Figures 
11 
thru 
17 
for appropriate wiring dia- 
gram. 










