Submittal Sheet

© 2008 U.S. Boiler Company, Inc. - Lancaster, PA
Phone: 1-888-432-8887
Printed in the U.S.A.
Form No. PL81401171000-10/08-20Ms
Model
Input MBH
DOE Heating
Capacity (MBH)
I=B=R Net
Rating MBH
AFUE % (1)
Approx.
Shipping
Wt. (lbs.)
Min. Rec. Chimney Size
Round
Dia. (In.) x Ht. (Ft.)
Standing
Pilot
(EI) Electronic
Ignition
202* 38 31 27 80.0 82.3 222 4 x 15
202X* 50 42 37 80.2 83.2 272 4 x 15
203* 62 52 45 80.0 82.6 272 4 x 15
204* 96 80 70 80.1 82.3 316 5 x 15
205* 130 108 94 80.2 82.0 364 6 x 15
206* 164 136 118 80.3 81.7 424 6 x 15
207* 198 163 142 80.4 81.4 468 7 x 15
208* 232 191 166 80.4 81.2 524 7 x 15
209* 266 218 190 80.5 80.9 560 8 x 15
210* 299 244 212 80.7 80.6 618 8 x 15
203H* 62 52 45 N/A 84.0 274 4 x 15
204H* 96 80 70 N/A 84.0 319 5 x 15
205H* 130 108 94 N/A 84.0 368 6 x 15
206H* 164 136 118 N/A 84.0 429 6 x 15
Model A B C D E F G
202 18-3/4 10-3/4 6-3/8 4 45-1/2 8-1/2 10 (1)
202X 20 12 6 4 45-1/2 8-1/2 4-3/4
203 20 12 6 4 45-1/2 8-1/2 4-3/4
204 23-1/4 15-1/4 7-5/8 5 47-1/8 9-1/8 4-3/4
205 26-1/2 18-1/2 9-1/4 6 48-1/2 9-3/4 5-1/4
206 29-3/4 21-3/4 10-7/8 6 48-1/2 9-3/4 5-1/4
207 33 25 12-1/2 7 50-1/8 10-3/8 6-5/8
208 36-1/4 28-1/4 14-1/8 7 50-1/8 10-3/8 6-5/8
209 39-1/4 31-1/2 15-3/4 8 52 11 7-1/4
210 42-3/4 34-3/4 17-3/8 8 52 11 7-1/4
in inches
Ratings and Specifications
Dimensions
*When ordering, add suufix ‘N’ for natural gas, or’P’ for propane. Add ‘C’ for 24V standing pilot, or ‘I’ for electronic ignition. Electronic ignition is standard on 2H models. Water
only, 30 PSI maximum working pressure. For elevations above 2000 feet, reduce ratings four percent (4%) per 1000 feet above sea level. 15’ chimney height is from bottom of draft
hood opening to top of chimney. Refer to the National Fuel Gas Code, appendix G for equivalent areas of circular and rectangular flue linings.
(1) 202 only. Dimension ‘G’
includes allowance for 4” x 3”
reducer (furnished with boiler)