Install Instructions

68
More make-up water and higher concentrations of
contaminants damage the boiler sooner. Our warranty
does not cover corrosion and sediment-related
damage. Clearly it is in everyone's best interest to
prevent this type of failure. You can do your part by
ensuring that your system is leak-free, keeping leakage
to less than 2 percent of the boiler water volume each
month.
D. ATTENTION TO BOILER WHILE NOT IN
OPERATION.
NOTICE
If boiler is not used during winter time, it must be
fully drained to prevent freeze damage.
1. Spray inside surfaces with light lubricating or
crankcase oil using gun with extended stem so as to
reach all corners.
2. With steam boilers, at end of season add sufcient
water to ll boiler to top of water column and leave
it that way until fall when water should be drained
again to proper level. If at this time boiler water is
dirty, drain water, ush out boiler, and rell with
clean water to prescribed water level.
3. Always keep the manual fuel supply valve shut off
if the burner is shut down for an extended period of
time.
4. To recondition the heating system in the fall season
after a prolonged shut down, follow the instructions
outlined in Section X, Paragraphs A through K.
WARNING
This boiler contains controls which may cause the
boiler to shut down and not restart without service.
If damage due to frozen pipes is a possibility, the
heating system should not be left unattended
in cold weather; or appropriate safeguards and
alarms should be installed on the heating system
to prevent damage if the boiler is inoperative.
SECTION XIII: MAINTENANCE AND SERVICE INSTRUCTIONS (cont'd)