Installation Operating Instructions

21 of 60
Actual
Setting
Display Description
Range
Adjust Menu (1 of 1)
Section
C
MIX DSGN
The design supply water temperature used in the heat loss
calculation for the heating system.
(OUTDR DSGN OFF)
70 to 210°F
(21 to 99°C)
Default = 180°F (82°C)
C
80 to 220°F
(27 to 104°C)
Default = 200°F (93°C)
MIX MAX
The maximum supply water temperature for the mixing system.
(OUTDR DSGN OFF)
C
OUTDR DSGN
The design outdoor air temperature used in the heat loss calculation
for the heating system. For setpoint operation, set the OUTDR
DSGN to OFF
-60 to 32°F, OFF
(-51 to 0°C, OFF)
Default = OFF
C
BOIL MIN
The minimum boiler return water temperature.
135 to 230°F
(57 to 110°C)
Default = 135°F (57°C)
C
WWSD
The systems warm weather shut down during the occupied (Day)
period.
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F (21°C)
35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)
ROOM
The desired room air temperature.
(OUTDR DSGN OFF)
C
C
MIX TARGET
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
60 to 200°F
(16 to 93°C)
Default = 180°F (82°C)
C
MIX MIN
The minimum supply temperature for the mixing system.
(OUTDR DSGN OFF)
OFF, 35 to 150°F
(OFF, 2 to 66°C)
Default = OFF
C
30 to 230 seconds
Default = 50 seconds
Delay Open
Open Delay
The time the actuating motor requires to operate from fully closed
to fully open.
Delay
C
BOIL MIN Delay
The amount of time the boiler requires to heat up to the boiler
minimum temperature from a cold start.
210 to 540 seconds
(10 second increments)
Default = 540 seconds
Delay
C
Pump Delay
The amount of time the boiler recirculating pump purges the boiler.
0 to 240 seconds
Default = 30 seconds
C
Temperature Units
The units of measure that all of the temperatures are to be displayed
in the control.
°F, °C
Default = °F