Submittal Sheet

© 2007 U.S. Boiler Company, Inc. - Lancaster, PA
Phone: 1-888-432-8887
www.burnham.com Printed in the U.S.A.
Form No. PL81401061000-3/07-10Mss
Ratings and Specifications
1. Ratings shown are for installations at sea level and elevations up to 2000 feet. Ratings reduce 4% for each 1000 ft. above sea level.
2. The Revolution is designed to vent directly through the wall or roof using Burnham’s approved vent systems, and AL29-4C
®
stainless steel pipe. Inlet air can be supplied using
single wall metal pipe or PVC pipe using Burnham’s PVC air intake kit.
Natural Gas or LP Gas
Boiler
Model
Input
(MBH)
DOE
Heating
Capacity
(MBH)
I = B = R
Net Rating
(MBH) AFUE (%)
Maximum Vent
Length
(Equiv. Ft.)
Maximum
Air Inlet
Length
Water
Capacity
(Gal.)
Approximate
Shipping
Weight
(Lbs.)
RV3
RV4
RV5
RV6
RV7
62
96
130
164
190
55
84
114
143
166
48
73
99
124
144
88.0
87.6
87.4
87.2
87.0
50
50
50
50
50
52
52
52
52
52
3.6
4.4
5.1
5.9
6.6
260
354
448
542
636
Boiler
Model A B C D
RV3 24-3/4 10 5-15/16 7-1/8
RV4 28 13-1/4 7-9/16 7-1/8
RV5 31-1/4 16-1/2 9-3/16 6-7/8
RV6 34-1/2 19-3/4 10-13/16 6-7/8
RV7 37-3/4 23 12-7/16 6-7/8
Dimensions
TOP VIEW FRONT VIEW
Boiler
Model
Gas Valve
Inlet
(NPT)
Water Supply
& Return
(NPT)
Air Inlet
Diameter
(In.)
Vent
Diameter
(In.)
RV3
RV4
RV5
RV6
RV7
1/2
1/2
1/2
3/4
3/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
3
3
4
4
4
3
3
3
3
3
Gas, Water and Vent Connections