Install Instructions

16
Figure 15: Wiring Diagram
VI. Electrical
A. General Install wiring and ground boiler in accordance
with requirements of authority having jurisdiction, or
in absence of such requirements the National Electrical
Code, ANSI/NFPA 70.
B. Install thermostat. Locate on inside wall
approximately4feetaboveoor.Donotinstallon
outsidewall,nearreplace,orwhereinuencedby
draftsorrestrictedairow,hotorcoldwaterpipes,
lightingxtures,television,orsunlight.Allowfreeair
movement by avoiding placement of furniture near
thermostat.
C. Wire thermostat. Remove transformer from junction
box. Provide Class II circuit between thermostat and
boiler. Connect circuit to blue wires to provide power
to thermostat. Connect circuit to brown wire to control
boiler operation. Set thermostat heat anticipator to 0.4
amps. See Figure 15.
D. Alliance SL™ Indirect Water Heater (if used) See
Figure 15, Ladder Diagram.
1. Attach extension junction box to junction box.
2. Provide two wire circuit between junction box and
temperature limit control (See Section III: Steam
Piping and Trim, Paragraph E.2). Use one red and
one orange wire if possible. Refer to Alliance SL™
Installation, Operating and Service Instructions.
E. Wire boiler. Boiler is rated for 120 VAC, 60 hertz,
less than 12 amperes. A separate electrical circuit
must be run from the main electrical service with an
over-current device/disconnect in the circuit.
Connect circuit to black and white wires and green
ground screw. A service switch is recommended
and may be required by some local jurisdictions.
See Figure 15.
F. Mount transformer on junction box.