Personnel Alert: Base Station
Setting the Dip Switch Addresses
Table 12. Address Switches
Dip Switch Position
- Open position indicates binary 0
- Close position indicates binary 1
Slave
Address
Binary
Equivalent
A7 A6 A5 A4 A3 A2 A1 A0
01 00000001 Open Open Open Open Open Open Open Close
02 00000010 Open Open Open Open Open Open Close Open
03 00000011 Open Open Open Open Open Open Close Close
04 00000100 Open Open Open Open Open Close Open Open
05 00000101 Open Open Open Open Open Close Open Close
06 00000110 Open Open Open Open Open Close Close Open
07 00000111 Open Open Open Open Open Close Close Close
08
.
00001000
.
Open
.
Open
.
Open
.
Open
.
Close
.
Open
.
Open
.
Open
.
21