User Manual

NÜO Flux Manual
Installation
6
NÜO FLUX
The NÜO FLUX readers incorporates a 4-pin male overhead connector and the corresponding female
connector which joins 3 metres of piped cable with 4 wires (2 twisted pairs). This means that the installation
and wiring to then connect the reader to a single door controller or to the corresponding Wili are both very
simple.
The built-in piped cable used to connect the reader has the following technical characteristics:
- Gauge: 0.22 mm
- Arrangement: 2 twisted pairs
- Resistance: <2 Ohms
A minimum distance of 12 cm must be maintained if installations are made with doors with 2 input/out-
put readers or with 2 readers that are very close together.
TYPE OF WIRING AND WIRING DISTANCE:
WIRING SPECIFICATIONS:
DISTANCE BETWEEN READERS:
The wiring distance from the reader and the single door controller or Wili should not exceed
15 metres in length.
Orange
O/W
Green
-
A
B
+
BY B US
G/W
3 metres of cable
NÜO FLUX