B-Box HV Installation Guide

BYD Battery-Box HV User Manual
6 Cleaning and Maintenance
6.1 Cleaning
It is recommended that the BYD Battery-Box HV system be cleaned periodically. If the enclosure is dirty, please use
a softdry brush or a dust collector to remove the dust. Liquids such as solvents, abrasives or corrosive liquids
should not be used to clean the enclosure.
6.2 Maintenance
6.2.1 Recharge Requirements During Normal Storage
Batteries should be stored in an environment with a temperature range between -10℃~+45, and maintained
regularly according to the following table with 0.5C (12.5A) current until 40% SOC after a long time of storage.
Recharge conditions when in storage
Storage environment
temperature
Relative humidity of storage
environment
Storage time
SOC
Below -10
/
prohibit
/
-10~25
5%~70%
≤12 months
30%≤SOC≤60%
25~35
5%~70%
≤6 months
30%≤SOC≤60%
35~45
5%~70%
≤3 months
30%≤SOC≤60%
Above 45
/
prohibit
/
6.2.2 Recharge Requirement When Over Discharged
Please recharge the over discharged batteries in a timeframe that is in accordance to the following table, otherwise
the over discharged battery modules will be damaged.
Recharge conditions when battery is over discharged
Storage Environment Temperature
Time Before Recharge is Necessary
-10~25
≤15 days
25~45
≤7 days
8