Instructions

79
For a temperature of less than -5.0 °C or more than +25.0 °C, the “GX107” will trigger an alarm.
The threshold setting area can be set from -400 to +1250.
If “Temp1” is set to = +1250, the top threshold is deactivated.
If “Temp2” is set to = -400, the lower threshold is deactivated.
Indication of prexes “+” and “-” before the gures is mandatory. Without the corre-
sponding prex, and error will be output.
An error will also be output if the value of “Temp2” is larger than “Temp1”.
Deleting the set thresholds
To delete the set thresholds, use the command:
RESET TEMPERATURE #1513
Checking settings
To verify the present settings, use the command:
TEST TEMPERATURE #1513
Hysteresis function:
As of rmware version 1.11d (the version number is in every answering text message), every
analogue measurement (ADC, TEMPERATURE, VOLTAGE) has a hysteresis to prevent multiple
alarms in case of measured value uctuations around the alarm value. Please observe the
corresponding chapter “Hysteresis”.