Owner manual

Document Number: 13057
Revision 28-Mar-02
www.vishay.com
16
Phawo...kS..
Vishay ESTA
Ph a w o s 1 / 2650 / 0.5k S - . . .
monitoring device *)
partial outputs
frequency (kHz)
total output (kVAr)
voltage (V or kV)
live casing (grounded casing: no entry Phawo 750/...
NON-PCB
water-cooled
all fi lm dielectric
power capacitor
*) ST = thermostat
DR = pressure switch
Medium Frequency Capacitors Water Cooled
ESTAfi lm
®
, SUBDIVIDED IN PARTIAL OUTPUTS, 150 - 10000Hz
DESIGN
All- lm winding in brass sheet welded casing;
Casing conductive, or grounded;
Casing varnish RAL 7033;
IP00, indoor;
Ambient temperature 1°C .... 50°C;
Out owing water temperature 40°C maximum;
Common terminal with 2 water-cooled current connections
M20;
Water tubing conductive;
A maximum of 8 partial outputs with connection bolts M12
or M20 (depending on application current);
Mounting in the upright or horizontal position;
Upon request, temperature or pressure monitoring;
165
water inlet
and outlet
rating plate
2 x ø 9.8
50
50
H
5
158
82.5
H
1
429
407
11 x 15
4 x 50
x) thermostat
369
44
65
x) upon request
cooling pipe
ø 12 x 1
TYPE DESIGNATION
} Not all types available.