Technical data

24
Specifications
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives
Parameter List
Parameter
Number
Parameter Name Description Factory Default
Basic Display Group
b001 Output Freq Output frequency present at T1, T2 & T3 (U, V & W) Read Only
b002 Commanded Freq Value of the active frequency command Read Only
b003 Output Current Output current present at T1, T2 & T3 (U, V & W) Read Only
b004 Output Voltage Output voltage present at T1, T2 & T3 (U, V & W) Read Only
b005 DC Bus Voltage Present DC bus voltage level Read Only
b006 Drive Status Present operating condition of the drive Read Only
b007 Fault 1 Code A code that represents a drive fault Read Only
b008 Process Display The output frequency scaled by parameter A160 [Process Factor] Read Only
b010 Output Power Output power present at T1, T2 & T3 (U, V & W) Read Only
b011 Elapsed MWh Accumulated output energy of the drive Read Only
b012 Elapsed Run Time Accumulated time that the drive has output power since the last A195 [Reset Meters] Read Only
b013 Torque Current Displays the torque portion of the output current Read Only
b014 Drive Temp Present operating temperature of the drive power section Read Only
b015 Elapsed kWh 0.0 to 100.0 kWh Read Only
Basic Program Group
P031 Motor NP Volts 20 to drive rated volts Based on Drive Rating
P032 Motor NP Hertz 15 to 320 Hz 60 Hz
P033 Motor OL Current 0.0 Amps to (Drive Rated Amps x 2) in units of 0.1 Amps Drive Rated Amps
P034 Minimum Freq 0.0 to 320.0 Hz 0.0 Hz
P035 Maximum Freq 0.0 to 320.0 Hz 60 Hz
P036 Start Source 7 settings; Keypad, 3-Wire, 2-Wire, 2-Wire Level Sensitive, 2-Wire High Speed, Comm Port,
2-Wire Level Sensitive with Enable
2-Wire Level Sensitive
P037 Stop Mode 8 settings; Ramp Clear Fault, Coast Clear Fault, DC Brake Clear Fault, DC Brake w/Shutoff Clear
Fault, Ramp, Coast, DC Brake, DC Brake w/Shutoff
Coast, CF (Clear Fault)
P038 Speed Reference 6 settings; Drive Keypad, Internal Freq, Analog Input 1, Analog Input 2, Preset Freq,
Communications Port
Analog In1
P039 Accel Time 1 0.00 to 600.00 seconds 20.00 Secs (0.3-150 HP)
60.00 Secs (200-350 HP)
P040 Decel Time 1 0.00 to 600.00 seconds 20.00 Secs (0.3-150 HP)
60.00 Secs (200-350 HP)
P041 Reset To Defalts Used to reset drive to factory default settings Ready/Idle
P042 Auto Mode 4 settings; No Function, Hand-Off-Auto, Local/Remote, Auto/Manual Hnd-Off-Auto
P043 Motor OL Ret 2 settings; Disabled, Enabled Disabled
Terminal Block Group
T051 Digital In1 Sel 29 settings; Not Used, Purge, Auto Mode, Local, Comm Port, PID Disable, PID Hold, PID Reset,
Preset Freq, Aux Fault, Clear Fault, RampStop Clear Fault, CoastStop Clear Fault, DCInjStop
Clear Fault, Anlg1 InCtrl, Anlg2 InCtrl, MOP Up, MOP Down, Acc & Dec 2, Current Lmt2, Force
DC, Mtr I-Lock 1, Mtr I-Lock 2, Mtr I-Lock 3, Mtr I-Lock 4, Cmd Reverse, Logic In 1, Logic In 2,
Damper Input
Purge
T052 Digital In2 Sel Local
T053 Digital In3 Sel Clear Fault
T054 Digital In4 Sel Comm Port
T055 Relay Out1 Sel 20 settings; Ready/Fault, At Frequency, MotorRunning, Hand Active, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Above Anlg 2, Above PF Ang, Anlg In Loss, ParamControl,
Retries Exst, NonRec Fault, Reverse, Logic In 1, Logic In 2, Aux Motor, Fault
Ready/Fault
T056 Relay Out1 Level 0.0 to 9999 0.0
T058 Relay 1 On Time 0.0 to 600.0 Secs 0.0 Secs
T059 Relay 1 Off Time 0.0 to 600.0 Secs 0.0 Secs
T060 Relay Out2 Sel 20 settings; Ready/Fault, At Frequency, MotorRunning, Hand Active, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Above Anlg 2, Above PF Ang, Anlg In Loss, ParamControl,
Retries Exst, NonRec Fault, Reverse, Logic In 1, Logic In 2, Aux Motor, Fault
MotorRunning
T061 Relay Out2 Level 0.0 to 9999 0.0
T063 Relay 2 On Time 0.0 to 600.0 Secs 0.0 Secs
T064 Relay 2 Off Time 0.0 to 600.0 Secs 0.0 Secs
T065 Opto Out Sel 19 settings; Ready/Fault, At Frequency, MotorRunning, Hand Active, Motor Overld, Ramp Reg,
Above Freq, Above Cur, Above DCVolt, Above Anlg 2, Above PF Ang, Anlg In Loss, ParamControl,
Retries Exst, NonRec Fault, Reverse, Logic In 1, Logic In 2, Fault
At Frequency
T066 Opto Out Level 0.0 to 9999 0.0
T068 Opto Out Logic 2 settings; NO (Normally Open), NC (Normally Closed) NO (Normally Open)
T069 Analog In 1 Sel 6 settings; Current Mode (0-20 mA), Current Mode (4-20 mA), Voltage Mode - Unipolar (0-10V),
Current Mode Square Root (0-20 mA), Current Mode Square Root (4-20 mA), Voltage Mode
Square Root - Unipolar (0-10V)
Voltage Mode - Unipolar
(0-10V)
T070 Analog In 1 Lo 0.0 to 100.0% 0.0%
T071 Analog In 1 Hi 0.0 to 100.0% 100.0%
T072 Analog In 1 Loss 7 settings; Disabled, Fault, Stop, Zero Ref, Min Freq Ref, Max Freq Ref, Preset Freq0 Disabled