Technical data

27
Specifications
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives
R239 Aux Motor Mode 2 settings; Disabled, Enabled Disabled
R240 Aux Motor Qty 6 settings; 1 Aux Mtr, 2 Aux Mtr, 3 Aux Mtr, 1 Mtr + Swap, 2 Mtr + Swap, 3 Mtr + Swap 1 Aux Mtr
R241 Aux 1 Start Freq 0.0 to 320.0 Hz 50.0 Hz
R244 Aux 2 Start Freq
R247 Aux 3 Start Freq
R242 Aux 1 Stop Freq 0.0 to 320.0 Hz 25.0 Hz
R245 Aux 2 Stop Freq
R248 Aux 3 Stop Freq
R243 Aux 1 Ref Add 0.0 to 100.0% 0.0%
R246 Aux 2 Ref Add
R249 Aux 3 Ref Add
R250 Aux Start Delay 0.0 to 999.9 Secs 5.0 Secs
R251 Aux Stop Delay 0.0 to 999.9 Secs 3.0 Secs
R252 Aux Prog Delay 0.00 to 60.00 Secs 0.50 Secs
R253 Aux AutoSwap Tme 0.0 to 999.9 Hr 0.0 Hr
R254 Aux AutoSwap Lvl 0.0 to 100.0% 50.0%
Advanced Display Group
d301 Control Source 0 to 99 Read Only
d302 Contrl In Status 0 to 1 Read Only
d303 Comm Status 0 to 1111 Read Only
d304 PID Setpnt Displ 0.0 to 100.0% 0.0%
d305 Analog In 1 0.0 to 120.0% 0.0%
d306 Analog In 2
d307 Fault 1 Code 0 to 122 Read Only
d308 Fault 2 Code
d309 Fault 3 Code
d330 Fault 4 Code
d331 Fault 5 Code
d332 Fault 6 Code
d333 Fault 7 Code
d334 Fault 8 Code
d335 Fault 9 Code
d336 Fault 10 Code
d310 Fault 1 Time-hr 0 to 32767 Hr Read Only
d312 Fault 2 Time-hr
d314 Fault 3 Time-hr
d337 Fault 4 Time-hr
d339 Fault 5 Time-hr
d341 Fault 6 Time-hr
d343 Fault 7 Time-hr
d345 Fault 8 Time-hr
d347 Fault 9 Time-hr
d349 Fault 10 Time-hr
d311 Fault 1 Time-min 0.0 to 60.0 Min Read Only
d313 Fault 2 Time-min
d315 Fault 3 Time-min
d338 Fault 4 Time-min
d340 Fault 5 Time-min
d342 Fault 6 Time-min
d344 Fault 7 Time-min
d346 Fault 8 Time-min
d348 Fault 9 Time-min
d350 Fault 10 Time-min
d316 Elapsed Time-hr 0 to 32767 Read Only
d317 Elapsed Time-min 0.0 to 60.0 Min Read Only
d318 Output Powr Fctr 0.0 to 180.0 deg Read Only
d319 Testpoint Data 0 to FFFF Read Only
d320 Control SW Ver 1.00 to 99.99 Read Only
d321 Drive Type Used by Rockwell Automation Field service personnel
d322 Output Speed 0.0 to 100.0% Read Only
d323 Output RPM 0 to 24000 RPM Read Only
d324 Fault Frequency 0.00 to 320.00 Hz Read Only
d325 Fault Current 0.0 to (Drive Rated Amps x 2) Read Only
Parameter
Number
Parameter Name Description Factory Default