Technical data

3
Product Overview
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives
Packaging
IP20, NEMA/UL Type 1 - For conventional mounting inside or
outside a control cabinet in a 45°C (113°F) ambient.
Flange Type - Frame C ratings through 15 kW (20 HP) @ 380-
480V AC and 7.5 kW (10 HP) @ 200-240V AC allow for mounting
heatsink through back of an enclosure, thus removing a large
portion of the heat inside a cabinet. The backside is rated IP66,
NEMA/UL Type 4X/12 for both indoor and outdoor use.
Installation flexibility is enhanced by the UL Plenum rating
allowing for direct mounting in an air handling system.
I/O
Three (3) semi-programmable and four (4) fully programmable
digital inputs provide application versatility.
Two (2) programmable form C relay outputs and one (1) opto
output can be used to indicate various drive or motor conditions.
Two (2) analog outputs are DIP Switch selectable for either
voltage (0-10V) or current (0-20 mA). These scalable, 10-bit
outputs are suitable for metering or as a speed reference for
another drive.
Two (2) analog inputs (one unipolar and one bipolar) are DIP
switch selectable for either voltage or current. One input is
isolated from the rest of the drive I/O.
Six (6) programmable form A relay outputs are available via user
installed Auxiliary Relay Board (Frames D through H only).
Operator Keypad and Programming
Integral keypad features 2 line, 16 character LCD display.
LED indicators provide system configuration and fault status.
Configurable Hand/Off/Auto function buttons.
Digital increase/decrease speed control.
Parameter names are displayed as text.
Parameters are grouped into files based upon function, making
programming fast and easy.
Function Loss
Run/FWD
Software Enable
Digital Common
Digital Input 1 (Purge)
Digital Input 2 (Local)
Digital Input 3 (Clear Fault)
Digital Input 4 (Comm Port)
Digital Common
Opto Common
+ 24VDC
+ 10VDC
Analog Input #1
Analog Common #1
Analog Output #1 (Frequency 0-10V)
Analog Output #2 (Output Current 0-10V)
Analog Input #2
Analog Common #2
Opto Output (At Frequency)
RJ-45 Shield
#1 Relay N.O. (Ready/Fault)
#1 Relay Common
#1 Relay N.C.
#2 Relay N.O. (Motor Running)
#2 Relay Common
#2 Relay N.C.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 R1 R2 R3 R4 R5 R6
AO1
10V 20MA
AO2
10V 20MA
AI1
10V 20MA
AI2
10V 20MA
SNK
SRC
Control Board
Hand Auto
Purge
Interlocks
Auto Start
Freeze/Fire
Stats
+ –