Call Systems

Declaration of Performance • Approved Document No. DOP0000005 R1 Page 2 of 3
has performed type testing and the initial inspection of the manufacturing plant and of factory
production control with continuous surveillance, assessment and approval of the factory
production control under system 1 and issued following certificate of constancy of
performance:
0359-CPD-0183
8. In case of the declaration of performance concerning a construction product for which a
European Technical Assessment has been issued:
Not applicable, see item 7
9(a). Declared performance applicable to models C4403AIR, C4403A2, C4403B and C4416:
All requirements including all Essential Characteristics and the corresponding performances for the
intended use or uses indicated in 3. above have been determined as described in the hEN mentioned
in the following table.
Essential characteristics
Performance
Clauses in EN54-
5:2000 + A1:2002
Notes
Nominal activation
conditions/Sensitivity, Response delay
(response time) and Performance
under fire conditions
Pass
4.2, 4.3, 5.2 to 5.6,
5.8, 6.1, 6.2
6.2 applies to
C4403A1R only
Operational reliability
Pass
4.4 to 4.11
Tolerance of supply voltage
Pass
5.7
Durability of operational reliability
(temperature resistance)
Pass
5.9, 5.10
Durability of operational reliability
(vibration resistance)
Pass
5.14 to 5.17
Durability of operational reliability
(humidity resistance)
Pass
5.11, 5.12
Durability of operational reliability
(corrosion resistance)
Pass
5.13
Durability of operational reliability
(electrical stability)
Pass
5.18
Note: ActiV detector model number C4414 (Multi-Sensor Fire Detector) also has a declared
performance in section 9(b) relating to EN54-7:2000 + A1:2002 +A2:2006