SmartSwitch 9000 9C214-2 DC Power Supply Installation Guide 9031305-05
Notice Notice Cabletron Systems reserves the right to make changes in specifications and other information contained in this document without prior notice. The reader should in all cases consult Cabletron Systems to determine whether any such changes have been made. The hardware, firmware, or software described in this manual is subject to change without notice.
Notice FCC Notice This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules.
Notice DECLARATION OF CONFORMITY ADDENDUM Application of Council Directive(s): Manufacturer’s Name: Manufacturer’s Address: European Representative Name: European Representative Address: Conformance to Directive(s)/Product Standards: Equipment Type/Environment: 89/336/EEC 73/23/EEC Cabletron Systems, Inc. 35 Industrial Way PO Box 5005 Rochester, NH 03867 Mr. J.
Notice iv
Contents Chapter 1 Introduction Using This Manual........................................................................................................ 1-1 The 9C214-2 Power Supply.......................................................................................... 1-1 Features ................................................................................................................... 1-3 Power Distribution System...............................................................................
Contents vi
Chapter 1 Introduction Using This Manual Read through this manual to become familiar with its contents and gain an understanding of the features and capabilities of the 9C214-2 Power Supply prior to installation and operation. Chapter 1, Introduction, provides a brief description of the 9C214-2 Power Supply and its features. This chapter also includes a list of related manuals and information on getting help.
Introduction P W R S N B STATUS 100% Load 9C214-2 -OL SMB Status LED 50% Power Supply Status LED 0% POWER SUPPLY MODULE GML Power Supply Level Indicator LED THIS UNIT TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN ACCORCANCE WITH THE NEC OR THE AUTHORITY HAVING JURISDICTION ! 48/60V 30A MAX Circuit Breaker Terminal Block Figure 1-1.
Introduction Features Diagnostic Controller for Management Each 9C214-2 Power Supply has a diagnostic controller. This diagnostic controller includes a microprocessor that monitors the numerous power supply functions available to the Network Manager via the LCD on the 9C300-1 Environmental Module, as well as local and remote management functions.
Introduction Power Distribution System The SmartSwitch 9000 uses a distributed DC power system (Figure 1-2) similar to those used in super computers. Three separate power buses are used to distribute DC power. The 48 volt DC System Power Bus, located on the backplane, powers all modules and the system cooling fans. The Diagnostic Power Bus provides 5 volts DC to all of the system’s diagnostic controllers and the environmental module. The INB termination power bus provides 3.
Introduction Related Manuals The manuals listed below should be used to supplement the procedures and technical data contained in this manual. SmartSwitch 9000 Installation Guide SmartSwitch 9000 Operations Guide SmartSwitch 9000 9C300-1 Environmental Module User’s Guide In addition, each Interface Module has a user’s guide. Getting Help For additional support related to this device or document, contact the Cabletron Systems Global Call Center: Phone (603) 332-9400 Internet mail support@ctron.
Introduction 1-6
Chapter 2 Installing the 9C214-2 Power Supply ! CAUTION This unit to be installed in a restricted access area in accordance with the NEC or the authority having jurisdiction. When installing the unit the following guidelines must be met: • • • • Connect to a 48Vdc SELV source which is reliably connected to earth ground. The branch circuit over current protection must be rated max 30A. Use #10AWG copper conductors only.
Installing the 9C214-2 Power Supply 5. Remove the cover. (Keep the cover in the event you need to remove the power supply. The cover must be replaced to protect the connector.) 6. Hold the power supply by the handles on the top and bottom of the unit, and do the following: a. Align the power supply so that the lip on the bottom and the hook on the top are slightly above the corresponding slots on the chassis. b.
Installing the 9C214-2 Power Supply Slot on Chassis 2 1 Securing Screws . . . . . . . . . . . P W R S N B STATUS 100% Load 9C214-2 -OL 50% 0% POWER SUPPLY MODULE GML . . . . . . . . . . . THIS UNIT TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN ACCORCANCE WITH THE NEC OR THE AUTHORITY HAVING JURISDICTION Terminal Block ! Tab 48/60V 30A MAX Securing Screws Figure 2-1.
Installing the 9C214-2 Power Supply Connecting Power Source A nominal 48 or 60 volt positive or negative power source can be connected to a 9C214-2 Power Supply. Follow the appropriate steps starting below to make the proper connection.
Installing the 9C214-2 Power Supply Connecting a Nominal -48/-60 Volt Negative Power Source The nominal -48/-60 volt negative power source is connected to a 9C214-2 Power Supply using at least number 10 AWG (5 square millimeters) copper wire to which ring or spade terminals that will accept a number ten screw have been attached. Connect the power source to the connections on the terminal block on the 9C214-2 Power Supply (Figure 2-3) by following the steps below. 1.
Installing the 9C214-2 Power Supply Powering Up a 9C214-2 Power Supply NOTE Before you power up a 9C214-2 Power Supply, make sure that the Environmental Module and all modules have been properly installed. 1. Turn on the 9C214-2 Power Supply using the circuit breaker at the bottom right of the power supply. (The power supply uses a soft start feature and does a pre-power diagnostic check. Outputs become enabled within 5 seconds of power on.) 2. Check to make sure that a. The PWR Status LED is green. b.
Chapter 3 9C214-2 Power Supply Operation The 9C214-2 Power Supply can operate with input voltages ranging from 36 – 72 positive or negative Volts Direct Current (VDC). Each 9C214-2 provides a maximum of 1000 watts of power to the SmartSwitch 9000. When two or more power supplies are installed, the system uses a current sharing scheme where under all load conditions each supply provides power equally.
9C214-2 Power Supply Operation Diagnostic Controller The diagnostic controller is composed of a Z-80 microprocessor and it’s supporting logic. The diagnostic controller is designed to monitor the power supply’s input and output power parameters as well as the temperature and fan status. In addition, the diagnostic controller adjusts fan speed and controls the LANVIEW diagnostic LEDs.
9C214-2 Power Supply Operation P W R S N B STATUS 100% Load 9C214-2 SMB STATUS LED -OL PWR STATUS LED 50% Power Supply Level Indicator LED 0% POWER SUPPLY MODULE GML Figure 3-1. 9C214-2 Power Supply LANVIEW LEDs The PWR Status LED indicates, by color, the status of a power supply’s input and outputs. The possible colors, states, and descriptions of the PWR Status LED are listed in Table 3-1. Table 3-1.
9C214-2 Power Supply Operation The SMB Status LED indicates, by color, the status of the diagnostic controller. The possible colors, states, and descriptions of the SMB Status LED are listed in Table 3-2. Table 3-2. SMB Status LED LED Color 3-4 State Description Green Functional Fully operational. Yellow/Green Booting Flashes yellow and green while booting. Yellow Testing Power up testing being performed.
9C214-2 Power Supply Operation The Power Supply Level Indicator LED indicates, by segment number, the percentage of the power supply’s capacity being used. The possible states and descriptions of the Power Supply Level Indicator LED are listed in Table 3-3. Table 3-3. Power Supply Level Indicator LED Segment Number(s) LED Color State Description 1-5 Green 0–49% of power load being used. No action necessary. 6-9 Green 50-89% of power load being used. No parallel power supply operational.
9C214-2 Power Supply Operation 3-6
Chapter 4 Specifications Safety ! CAUTION It is the responsibility of the person who sells the system to which the modules will be a part to ensure that the total system meets allowed limits of conducted and radiated emissions. The 9C214-2 Power Supply, when properly installed on the SmartSwitch 9000 Chassis, complies with the following specifications and standards: Safety Requirements of: • • • • • UL 1950 CSA C22.2 No.
Specifications Service The 9C214-2 Power Supply is designed with the following service capability: MTBF (MIL-STD-217): >200,000 hours projected MTTR: <.50 hour Bellcore Standards The 9C214-2 Power Supply, when properly installed on the SmartSwitch 9000 Chassis, complies with the following standards: TR-NWT-000063Network Equipment Building System (NEBS) Generic Equipment Requirements GR-1089-COREEMC and Electrical Safety Generic criteria for Network Telecommunications Equipment. Physical Dimensions 60.
Specifications DC Input Each 9C214-2 Power Supply operates with the following voltage and current. Voltage 36–72 VDC Current 30A DC Maximum Fusing The DC input to the 9C214-2 Power Supply has a built in 30 amp circuit breaker. DC Input Connection The DC input connector is a three connector terminal block.
Specifications 4-4