Operating instructions

B. GROUNDING
Permanently ground boiler according to local codes and the current edition of The National Electrical Code. Run a 14 gage or heavier copper wire
from boiler to a grounded connection in service panel or a properly driven and electrically grounded ground rod.
C. ELECTRICAL POWER SUPPLY
WARNING: Turn off electric power at fuse box before making any line voltage connections. Follow local electric
codes. Failure to follow this warning could result in electrical shock, personal injury, or death.
All electrical work must conform to local codes as well as the National Electrical Code. If not familiar with wiring and codes in general, have a
competent electrician do this job.
Boiler controls are all wired at the factory. All that is required is to connect a 115-v electric supply and thermostat wires to aquastat relay.
Run a separate circuit from a separate overcurrent protective device in electrical service entrance panel. This should be a 15-amp circuit. Locate
a shutoff switch at boiler. It must be turned OFF during any maintenance. Solder and tape or securely fasten these connections with wire nuts.
D. CONNECTING 115V ELECTRICAL WIRING TO BOILER
Connect 115-v electric supply wires to terminals L1 and L2 on aquastat relay. (See Fig. 14.)
E. THERMOSTAT CONNECTIONS
The 2 wires from thermostat connect to terminals T and T on L8148A and L8124C aquastat relay (See Fig. 14.)
Table 5Recommended Minimum Chimney Sizes
FIRING RATE (GPH) CHIMNEY HEIGHT (FT) NORMAL CHIMNEY AREA (IN.)
ROUND LINER
INSIDE DIAMETER (IN.)
SQUARE LINER
INSIDE DIMENSIONS (IN.)
0.60 to 1.30 15 8 X 8 6 6-3/4 X 6-3/4
1.31 to 1.80 15 8 X 8 7 6-3/4 X 6-3/4
1.81 to 2.00 20 8 X 8 8 6-3/4 X 6-3/4
For elevations above 2000 ft above sea level, add 3 ft to chimney heights. (See Fig. 12.)
Fig. 12Typical Chimney Requirements
A95601
MUST BE REQUIRED MINIMUM
HEIGHT. MUST BE AT LEAST
3 FT HIGHER THAN HIGHEST
PART OF PASSAGE THROUGH
ROOF. MUST BE AT LEAST 2 FT
HIGHER THAN ANY NEIGHBORING
OBJECT. MUST HAVE AN
UNOBSTRUCTED TOP OPENING.
MUST BE AT LEAST
4 IN. THICK AND BE TIGHT.
BALANCED
WEIGHT
CRIMPED
END
ALTERNATE POSITIONS
TOP
TOP
MUST SLOPE UP AT
LEAST
1
/4 IN. PER FOOT
OF HORIZONTAL RUN.
TIGHT CLEAN-OUT
DOOR
SEALED IN
THIMBLE
TIGHT, SMOOTH,
CORRECTLY SIZED.
DRAWBAND LAST
PIECE INSTALLED
DRAFT REGULATOR
VANE
11