Operating instructions
MAINTENANCE
To assure trouble-free operation, we recommend that flue passages, burner, combustion chamber area (target wall and fire door insulation), burner
adjustment, operation of controls, and boiler seals (door gasket or silicone seal, cast iron seals and flue collector) be checked ONCE EACH YEAR
by a competent service technician.
BEFORE THE START OF EACH SEASON (or whenever system has been shut down for some time), recheck the whole system for leaks and
recheck boiler and vent pipe for leaks. Replace or patch any boiler seals that are faulty.
WARNING: Never burn garbage or paper in the unit, and never leave combustible material around it.
PROCEDURE 1—RELIEF VALVE
This valve should open automatically when system pressure exceeds the safe limit (30 psi). Should it ever fail to open under this condition, shut
system down. Drain it until pressure is reduced below safe limit, then have valve replaced immediately. The relief valve should be tested monthly
during heating season. Prior to testing, make certain a discharge pipe is properly connected to the valve outlet and arranged so as to contain and
safely dispose of boiler discharge. Hold the trip lever fully open for at least five seconds in order to flush free any sediment that may lodge on
the valve seat. Then permit the valve to snap shut.
PROCEDURE 2—CONVENTIONAL EXPANSION TANK
As previously noted, this tank may become waterlogged or may receive an excess of air. Frequent automatic opening of relief valve indicates
waterlogging. A high boiler temperature accompanied by unusually low radiation unit temperature (and ″knocking″) indicates excess air in tank.
Fig. 17—Beckett Burner Electrode Adjustments (For V1 280 Heads)
UNIT SIZE HEAD
DIMENSIONS (IN.)
N H (HEAD TO NOZZLE)
140 F0, F3 1/16 7/32 to 9/32
210
V1
1/16
7/32 to 9/32
280 1/16
A01064
5/16 ABOVE
NOZZLE
ELECTRODE
DIMENSION “N”
SEE FIG 18
DIMENSION “H”
SEE BELOW
5/32
GAP
L1 OR V1 HEAD
LOCATION OF HEAD
AT "0" POSITION
ON ADJUSTING PLATE
WITNESS
MARK
HOLD DOWN
SCREW
PRIMARY
ADJUSTING
PLATE
SECONDARY
ADJUSTING
PLATE
KNURLED
NUT
ACORN NUT/
LOCK WASHER
"MD" AIR
TUBE COMBINATION
"V1" ADJUSTABLE
HEAD
1
3
⁄4″ ±
1
⁄32″
DIMENSION "Z"
A01064
Fig. 18—Beckett Burner Setting Variable (V1) Head
7/16 ABOVE
DIMENSION “N”
SEE FIG 18
NOZZLE
ELECTRODE
5/32
GAP
A95604
Fig. 19—Beckett Burner Setting Variable (V1) Head — 280
—17—
→
→
→