BOILER RATINGS AND CAPACITIES
BOILER MODEL NO.
INPUT
**HEATING
CAPACITY
*Mbh
‡NET
AHRI
RATING
WATER
*Mbh
A.F.U.E.
++
NO.
SEC.
Boiler
Water
Capacity
(US Gal.)
DIMENSIONS
(inches)
+gph *Mbh ABC
»BW(4,5)(B,R)AH-91 0.65 91 80 70 86.3 3 9.6 14½ 6 8
»BW(4,5)(B,R)AH-105 0.75 105 92 80 85.2 3 9.6 14½ 6 8
BW(4,5)(B,R)AH-140 1.00 140 120 104 84.0 3 9.6 14½ 6 8
»BW(4,5)(B,R)AH-126 0.90 126 111 97 86.0 4 11.6 17¾ 6 9
»BW(4,5)(B,R)AH-175 1.25 175 151 131 85.0 4 11.6 17¾ 6 9
BW(4,5)(B,R)AH-210 1.50 210 179 156 84.0 4 11.6 17¾ 6 9
»BW(4,5)(B,R)AH-168 1.20 168 147 128 86.5 5 13.7 21 6 11½
BW(4,5)(B,R)AH-245 1.75 245 210 183 84.3 5 13.7 21 6 11½
* Mbh = 1,000 BTU per hour [BTU = British Thermal Unit]
**Heating Capacity based on 13% CO
2
with a 0.02” w.c. draft over re, and a #1 smoke or less. Testing was done in
accordance with the D.O.E. (Department of Energy) test procedure.
+ gph = Gallons per hour oil at 140,000 BTU per gallon
++A.F.U.E. = Annual Fuel Utilization Ef ciency based upon D.O.E. test procedure.
Net AHRI Water Ratings based on piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.
>>
As Energy Star Partner, manufacturer has determined this product meets Energy Star guidelines for energy ef ciency.
BOILER RATINGS AND CAPACITIES
Figure 1 - Dimensions