Operating Instructions and Installation Instructions
34
AQUOS - IBIS - IDRON
EN
12
PRELIMINARY NOTIONS
12.1 SYSTEM CONFIGURATIONS DEPENDING ON THE MODEL
Upon installation, the product must be set according to the type of system, selecting the appropriate parameter
in the “SETTINGS” menu.
The possible congurations are 5, as described below:
CONFIGURATION DESCRIPTION
1
Room temperature management via the boiler probe or by enabling the external room
thermostat.
2
2.1 Room temperature management via the boiler probe or by enabling the external room
thermostat; instantaneous DHW production with plate heat exchanger.
2.2 Room temperature management via the boiler probe or by enabling the external room
thermostat; instantaneous hot domestic water production for boiler or storage tank with
thermostat (optional).
3
Room temperature management via boiler probe or enabling the external room thermostat;
boiler hot domestic water production with ntc probe (10 kΩ ß3435).
4 External Puffer management controlled by thermostat.
5 External Puffer management controlled by ntc probe (10 kΩ ß3435).
Fig. 29 - Conguration 1 (factory setting for heating version only)