WOOD COOKING STOVES
EN
the adjacent room and it must be provided with a solid and condensation collection chamber under the
entrance, accessible through the sealed metal gate.
The inner section of the chimney ue can be round (the best one) or square and the jointed sides must have
a minimum radius of 20 mm.
The section dimension must be minimum Ø150 mm and maximum Ø240 mm.
Made the efciency of the chimney ue overhauled by an expert stove-repairer and if necessary cover the
chimney ue with materials in compliance with current regulations.
The ue system must be placed on the roof.
The chimney ue must be provided CE in accordance with EN 1443 regulation. Please nd attached an
example of label:
Fig. 2 - Example of label
8.4 HEIGHT-DEPRESSION
The depression (draught) of a chimney ue depends also on its height. Check the depression with the values
provided at FEATURES page 27. Minimum height 3,5 meters.
8.5 MAINTENANCE
The chimney ue must be cleaned, since the soot and unburnt oil deposits reduce its section so blocking the
draught. In great quantities they can are up.
The fumes extraction pipes (fumes conduit + chimney ue + chimney pot) must always be cleaned, scrubbed
and checked by an expert stove-repairer, in compliance with current regulations, with the instructions of the
stove-manufacturer and the directives of your insurance company.
In case of doubts, please follow the most restrictive regulations.
Have your chimney ue and chimney pot checked and cleaned by an expert chimney sweep at least once
a week. The chimney sweep has to release a written declaration about the security of the system.
Not cleaning compromise safety.
8.6 CHIMNEY POT
Fig. 3 - Anti-wind chimney pots
The chimney pot is important for the correct running of the heating appliance:
We recommend using an anti-wind chimney pot, see Fig. 4 page 7.
The hole width for fumes exhaust must be the double of the chimney ue width and tted in a way that the
fume exhaust is assured also in case of wind.
It should prevent the inltration of rain, snow and animals.
The outlet height in the atmosphere must be away from the reux area caused by the roof structure or by
obstacles laying nearby (see TECHNICAL FEATURES page 6).