Operating Instructions and Installation Instructions

10
VEGA - SIRE
3
PLUS - DOGE
3
PLUS - SFERA
3
- SFERA
3
PLUS - PRINCE
3
- PRINCE
3
PLUS - GLOBE - TREND - ELISE
3
PLUS
EN
LEGEND Fig. 6 page 9
1 Room to ventilate
2 External air inlet
The room must be endowed with an external air recycling for a good climate in your ambient.
The air inow from outside to the inner occurs directly, through an opening on the external wall of the room
(see Fig. 6 page 9).
Bedrooms, garages, and store of ammable materials are excluded.
The air inlet should have a total net surface of 80 sqcm
2
: the aforesaid surface is to widen if inside the room
there are other activated appliances (for example: electric ventilators for foul air suction, cooker hoods, other
stoves, etc...) which depress the environment.
At switched on appliance it is necessary to check that the pressure fall between the room and the outside
does not exceed 4,0 Pa value: if necessary widen the air inlet (EN 13384).
The air inlet must be realized at a height close to the oor with an external grid against birds. In such a way it
cannot be obstructed by any object.
In case of installation with sealed-chamber the air inlet is not necessary.
9.9 COMBUSTIBLE AIR INLET FOR SEALED-CHAMBER INSTALLATION
Fig. 7 - Air inlet for sealed-chamber installation
LEGEND Fig. 7 page 10
1 ≥ 1,5 mt
2 ≥ 0,3 mt
3-3 Sectional view
4 Shield grid
5 Curve inlet to turn downwards
Check FEATURES page 43 if the purchased stove has a sealed-chamber. If the stove is endowed with a sealed-
chamber and you want also the whole installation with sealed chamber, please read the following instructions:
It is necessary to extract the air for combustion directly from outside.
Use a tube with minimum Ø60 mm and maximum 2 meters lenght; to connect see the back of the stove.
French standards require installation in double-walled ues (concentric system). The combustion air is drawn
from the cavity.
During installation step is necessary to verify the minimum distances required for the combustible air inlet as
(for example) an open door or window causes a vortex which could remove the combustible air necessary
to the stove (see the underlying scheme).
On the external wall it is necessary to install a curve at 90° to protect the combustible air inow from wind
effects: turn the curve inlet downwards, see Fig. 7 page 10.
Endow the curve with an external shield grid against birds in such a way that it cannot be obstructed by any
object.
Check with your local authorities if exists any restrictive regulation regarding the combustible
air inlet: if present, they must be applied