4.10 Control Terminal Connections
Main Terminal Strip
1 +24V +24V User Input / Output 100mA User Output
2 DI 1 Input 1 Digital 8 - 30 Volt DC
3 DI 2 Input 2 Digital 8 - 30 Volt DC
4 DI 3 Input 3 Digital 8 - 30 Volt DC
5 +10V +10 Volt User Output 10mA for user potentiometer
6 AI 1 Input 4 Digital 8 to 30DC/Analog Input 1, -10 to +10V, 0/4 to 20mA or =24VDC Digital
7 0V 0 Volt Common
8 AO1 Output 1 1st Analog/Digital Output, 0 to 10V, 4 to 20mA or +24DC Digital
9 0V 0 Volt Common
10 AI 2 Input 5 Digital 8 to 30V DC / Analog Input 2, 0 to 10V, 0/4 to 20mA or
11 AO2 Output 2 Analog input 2 / Digital Output, 0 to 10V, 4 to 20mA, Digital 24V
12 STO+ Drive hardware inhibit “Safe” 24V input - must be linked to ext +24 Volt (18-30 Volt) DC to
enable power stage
13 STO- Inhibit 0V input 0V return for the 24V “Safe” (STO)
Additional Terminal Strip
14 RL1-C Relay Output 1 Common Relay contacts, 250V AC, 30V DC, 5A
15 RL1-NO Relay Output 1 NO Relay contacts, 250V AC, 30V DC, 5A
16 RL1-NC Relay Output 1 NC Relay contacts, 250V AC, 30V DC, 5A
17 RL2-A Relay Output 2 Common Relay contacts, 250V AC, 30V DC, 5A
18 RL2-B Relay Output 2 NO Relay contacts, 250V AC, 30V DC, 5A