AC Supply Connection
3 Phase Units : Connect L1, L2, L3, PE
1 Phase Units : Connect L1, L2, PE
Supply Voltage
200 - 240 Volts +/- 10%
380 - 380 Volts +/- 10%
Fuses or MCB
Check the drive rating information on pages 41 & 42
Fuses or MCB
Control Terminals
Based on the factory default parameter settings
1 2 5 6 7
Run - Stop
Close the
switch to run
(enable), open
to stop
10K Speed
Pot
Motor Cable
For correct cable size, see technical data on pages 41
& 42
Observe the maximum permissible motor cable length
For motor cable lengths > 50 metres, an output filter
is recommended
Use a screened (shielded cable)
Motor Connection
Check for Star or Delta Connection
Enter the Motor Nameplate data into the drive param-
eters as follows:
l
Motor Rated Voltage : P1-07
l
Motor Rated Current : P1-08
l
Motor Rated Frequency : P1-09
l
Motor Rated Speed (Optional) : P1-10
M
Display
Help Card
Keypad Operation can be found on page 20
IMPORTANT
Safe Torque Off (STO) Function
1 9 12 13
Inhbit
stop
Link the terminals as shown, through the emergency stop
circuit contacts
Easy Start Up Guide: QD:Neo IP20