Installation & Operating Instructions
Page 27
P1-11 V/F Mode Voltage Boost
0.0 Drive Rating Dependent %
Voltage boost is used to oncrease the applied motor voltage at low output frequencies, in order to improve low speed and
starting torque. Excessive voltage boost levels may result in increased motor current and temperature, and force ventilation
of the motor may be required.
An automatic setting (Auto) is also possible, whereby the Fenner QD:Neo will automatically adjust this parameter based on
the motor parameters measured during an autotune.
P1-12
Primary Command Source Mode
0 6 0 -
0: Terminal Control. The drive responds directly to the signals applied to the control terminals.
1 : Uni-directional Keypad Control. The drive can be controlled in the forward direction only using and external or remote
keypad
2 : Bi-Directional Keypad Control. The drive can be controlled in the forward and reverse directions using an external or
remote keypad. Pressing the keypad START button toggles between forward and reverse.
3 : PI Control. The output frequency is controlled by the internal PID controller
4 : Fieldbus Control. Control via Modbus RTU if no fieldbus interface option is present, otherwise control is from the
fieldbus option module interface.
5 : Slave Mode. The drive acts as a slave to a connected Fenner QD:Neo operating in master mode
6 : CAN bus Control. Control via CAN bus connected to the RJ45 serial interface connector.
P1-13
Digital Inputs Function Select
0 21 1 -
Defines the function of the digital inputs depending on the control mode setting in P1-12. See section 7.1 for more informa-
tion.
P1-14
Extended Menu Access Code
0 30000 0 -
Parameter access control. The following settings are applicable:
P1-14 = P2-40 = 101 Allows access to Parameter Groups 0-5