Operating instructions

ııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııı
www.fptgroup.com
Neo
Installation & Operating Instructions
Page 28
7. Digital Input Functions
7.1 Digital Input Configuration Parameter P1-13
P1-13 Digital Input 1
(Terminal 2)
Digital Input 2
(Terminal 3)
Digital Input 3
(Terminal 4)
Analog Input 1
(Terminal 6)
Analog Input 2
(Terminal 10)
0 User defined User defined User defined User defined User defined
1 O : Stop
C : Run
O : Forward
C : Reverse
O : Selected speed Ref
C: Preset speed 1, 2
Analog 1 speed refer-
ence
O : Preset speed 1
C : Preset speed 2
2
O : Stop
C : Run
O : Forward
C : Reverse
Digital Input 3 Analog Input 1 Analog Input 2 Preset Speed
Off Off Off Preset Speed 1
On Off Off Preset Speed 2
Off On Off Preset Speed 3
On On Off Preset Speed 4
Off Off On Preset Speed 5
On Off On Preset Speed 6
Off On On Preset Speed 7
On On On Preset Speed 8
3 O : Stop
C : Run
O : Forward
C : Reverse
O : Selected speed ref
C : Preset speed 1
Analog 1 speed reference Analog torque reference
4 O : Stop
C : Run
O : Forward
C : Reverse
O : Selected speed ref
C : Preset speed 1
Analog 1 speed reference
O : Decel ramp 1 (P1-04)
C : Decel ramp 2 (P2-25)
5
O : Stop
C : Run
O : Forward
C : Reverse
O : Selected speed ref
C :Analog input 2
Analog 1 speed reference Analog 2 speed reference
6 O : Stop
C : Run
O : Forward
C : Reverse
O : Selected speed ref
C : Preset speed 1
Analog 1 speed reference
External trip*
O : trip C : Run
7
O : Stop
C : Run
O : Forward
C : Reverse
Digital Input 3 Analog Input 1 Preset Speed
Off Off Preset speed 1
On Off Preset speed 2
Off On Preset speed 3
On On Preset speed 4
External trip*
O : trip C : Run
8
O : Stop
C : Run
O : Forward
C : Reverse
Digital Input 3 Analog Input 1 Preset Speed
Off Off Preset speed 1
On Off Preset speed 2
Off On Preset speed 3
On On Preset speed 4
O : Decel ramp 1 (P1-04)
C : Decel ramp 2 (P2-25)
9
O : Stop
C : Run
O : Forward
C : Reverse
Digital Input 3 Analog Input 1 Preset Speed
Off Off Preset speed 1
On Off Preset speed 2
Off On Preset speed 3
On On Preset speed 4
O : Selected speed ref
C : Preset speed 1 .. 4
10 O : Stop
C : Run
O : Forward
C : Reverse
Normally Open (N.O.)
Close to increase speed
Normally OPen (N.O.)
Close to reduce speed
O : Selected speed ref
C : Preset speed 1
11 O : Stop
C : Run Fwd
O : Stop
C : Run Rev
O: Selected speed ref
C : Preset speed 1,2
Analog 1 speed refer-
ence
O : Preset speed 1
C : Preset speed 2
12
O : Stop
C : Run Fwd
O : Stop
C : Run Rev
Digital Input 3 Analog Input 1 Analog Input 2 Preset Speed
Off Off Off Preset speed 1
On Off Off Preset speed 2
Off On Off Preset speed 3
On On Off Preset speed 4
Off Off On Preset speed 5
On Off On Preset speed 6
Off On On Preset speed 7
On On On Preset speed 8
13 O : Stop
C : Run Fwd
O : Stop
C : Run Rev
O : Selected speed Ref
C : Preset speed 1
Analog 1 speed reference Analog torque reference
14 O : Stop
C : Run Fwd
O : Stop
C : Run Rev
O : Selected speed ref
C : Preset speed 1
Analog 1 speed reference
O : Decel ramp 1 (P1-04)
C : Decel ramp 2 (P2-25)
15 O : Stop
C : Run Fwd
O : Stop
C : Run Rev
O : Selected speed ref
C : Aanalog input 2
Analog 1 speed reference Analog 2 speed reference
16 O : Stop
C : Run Fwd
O :Stop
C : Run Rev
O : Selected speed ref
C : Preset speed 1
Analog 1 speed reference
External trip*
O : trip C : Run