Operating instructions

ııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııı
www.fptgroup.com
Neo
Installation & Operating Instructions
Page 3
ııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııı
Page 3
www.fptgroup.com
Neo
Installation & Operating Instructions
Display
Keypad Operation can be
found on page 20
1 2 5 6 7
1 9 12 13
Link the terminals as shown,
through the emergency stop
circuit contacts
10K Speed
Pot
Run - Stop
Close the switch
to run (enable),
open to stop
M
Motor Cable
For correct cable size, see techni-
cal data on pages 41 & 42
Observe the maximum permis-
sible motor cable length
For motor cable lengths > 50
metres, an output filter is recom-
mended
Use a screened (shielded cable).
The shield should be bonded to
earth at both ends
Motor Connection
Check for Star or Delta Connection
Enter the Motor Nameplate data
into the drive parameters as
follows:
l
Motor Rated Voltage : P1-07
l
Motor Rated Current : P1-08
l
Motor Rated Frequency : P1-09
l
Motor Rated Speed (Optional) : P1-10
AC Supply Connection
200 - 240 Volts +/- 10%
380 - 480 Volts +/- 10%
L3 L1
Fuses or
MCB
Check the
drive rating
information on
pages 41 & 42
L2 PE
Control terminals
IMPORTANT
SAFE TORQUE OFF (STO)
Easy Start Up Guide: QD:Neo IP55