4 : Output Frequency >+ Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >=Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Output Torque >=Limit. Logic when the motor torque exceeds the adjustable limit
7 : Analog Input 2 Signal Level>= Limit. Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit.
Note: When using settings 4-7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will
switch to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal
falls below the value programmed in P2-17.
Analog Output Mode
8 : Output Frequency (Motor Speed). 0 to P-01
9 : Output (Motor) Current. 0 to 200% of P1-08
10 : Output (Motor) Power. 0 to 150% of drive rated power
11 : Output (Motor) Power. 0 to 150% of drive rated power
P2-14 Analog Output 2 (Terminal 11) Format
See Below
U 0-10
U 0-10 = 0 to 10V
U 10-0 = 10 to 0V
A 0-20 = 0 to 20mA
A 20-0 = 20 to 0mA
A -20 = 4 to 20mA
A 20- = 20 to 4mA
P2-15 User Relay 1 Output (Terminals 14, 15 & 16) Function Select
0 7 1 -
Selects the function assigned to Relay Output 1. The relay has three output terminals, Logic 1 indicates the relay is active,
and therefore terminals 14 and 15 will be linked together.
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3 : Output Frequency > 0.0Hz. Logic 1 when the drive output frequency to the motor exceeds 0.0Hz
4 : Output Frequency>= Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >=Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Output Torque >=Limit. Logic 1 when the motor torque exceeds the adjustable limit
7 : Analog Input 2 Signal Level>=Limit. 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
Note: When using signals 4-7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will
switch to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal
falls below the value programmed in P2-17.
P2-16 Adjustable Threshold 1 Upper Limit (Analog Output 1/Relay Output 1)
P2-17 200.0 100.0 %
P2-17 Adjustable Threshold 1 Lower Limit (Analog Output 1/Relay Output 1)
0.0 P2-16 0.0 %
Used in conjunction with some settings of Parameters P2-11 & P2-15
P2-18 User Relay 2 Output (Terminals 17 & 18) Function Select
0 8 0 -
Selects the function assigned to Relay Output 2. The relay has two output terminals. Logic 1 indicates the relay is active,
and therefore terminals 17 and 18 will be linked together
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3 : Output Frequency > 0.0Hz. Logic 1 when the drive output frequency to the motor exceeds 0.0Hz
4 : Output Frequency>=Limit. Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current>= Limit. Logic 1 when the motor current exceeds the adjustable limit
6 : Output Torque>=Limit. Logic 1 when the motor torque exceeds the adjustable limit
7 : Analog Input 2 Signal Level>=Limit. 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
8 : Hoist Brake Control. The relay can be used to control the motor holding brake on a hoist. Contact your local Fenner
Authorised Distributor for further information on this feature.
Note: When using settings 4-7, parameters P2-19 and P2-20 must be used together to control the behaviour. The output will
switch to Logic 1 when the selected signal exceeds the value programmed in P2-19, and return to Logic 0 when the signal
falls below the value programmed in P2-20
P2-19 Adjustable Threshold 1 Upper Limit (Analog Output 2/Relay Output 2)
P2-20 200.0 100.0 %
P2-20 Adjustable Threshold 1 Lower Limit (Analog Output 2/Relay Output 2)
0.0 P2-19 0.0 %
Used in conjunction with some settings of Parameters P2-13 & P2-18
P2-21
Display Scaling Factor -30.000 30.000 0.000 -