8.2 Parameter Group 3 - PID Control
Par Parameter Name Minimum Maximum Default Units
P3-01 PID Proportional Gain
0.1 30.0 1. 0 -
PID Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small
changes in the feedback signal. Too high a value can cause instability
P3-02 PID Integral Time Constant
0.0 30.0 1. 0 s
PID Controller Integral Time. Larger values provide a more damped response for systems where the overall process
responds slowly
P3-03 PID Differential Time Constant
0.00 1. 0 0 0.00 s
PID Differential Time Constant
P3-04 PID Operating Mode
0 1 0 -
0 : Direct Operation. Use this mode if an increase in the motor speed should result in an increase in the feedback signal
1 : Inverse Operation. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal
P3-05 PID Reference (Setpoint) Source Select
0 2 0 -
Selects the source for the PID Reference / Setpoint
0 : Digital Preset Setpoint. P3-06 is used
1 : Analog Input 1 Setpoint
2 : Analog Input 2 Setpoint
P3-06 PID Digital Reference (Setpoint)
0.0 100.0 0.0 %
When P3-05 = 0, this parameter sets the preset digital reference (setpoint) used for the PID Controller
P3-07 PID Controller Output Upper Limit
P3-08 100.0 100.0 %
Limits the maximum value output from the PID controller
P3-08 PID Controller Output Lower Limit
0.0 P3-07 0.0 %
Limits the minimum output from the PID controller
P3-09 PID Output Limit Control
0 3 0 -
0 : Digital Output Limits. The output range of the PID controller is limited by the values of P3-07 & P3-08
1 : Analog Input 1 Provides a Variable Upper Limit. The output range of the PID controller is limited by the values of P3-
08 & the signal applied to Analog Input 1
2: Analog Input 1 Provides a Variable Lower Limit. The output range of the PID controller is limited by the signal applied
to Analog Input 1 & the value of P3-07
3: PID output Added to Analog Input 1 Value. The output value from the PID Controller is added to the speed reference
applied to the Analog Input 1
P3-10 PID Feedback Signal Source Select
0 1 0 -
0 : Analog Input 2
1 : Analog Input 1
P3-11 Minimum PID Error to Enable Ramps
0.0 25.0 0.0 %
Defines a threshold PID error level, whereby if the difference between the setpoint and feedback values is less than the set
threshold, the internal ramp times of the drive are disabled. Where a greater PID error exists, the ramp times are enabled to
limit the rate of change of motor speed on large PID errors, and react quickly to small errors.
Setting to 0.0 means that the drive ramps are always enabled. This parameter is intended to allow the user to disable the
drive internal ramps where a fast reaction to the PID control is required, however by only disabling the ramps when a small
PID error exists, the risk of possible over current or over voltage trips being generated are reduced.
P3-12 PID Feedback Value Display Scaling Factor
0.000 50.000 0.000 -
Applies a scaling factor to the displayed PID feedback, allowing the user to display the actual signal level from a transducer,
e.g. 0 – 10 Bar etc.
P3-13 PID Feedback Wake Up Level
0.0 100.0 0.0 %
Sets a programmable level whereby if the drive enters standby motor whilst operating under PID control, the selected
feedback signal must fall below this threshold before the drive will return to normal operation.
P3-14 Reserved Parameter
- - - -
No function