8.4 Parameter Group 5 - Communication Parameters
Par Parameter Name Minimum Maximum Default Units
P5-01 Drive Fieldbus Address
0 63 1 -
Sets the fieldbus address for the Fenner QD:Neo
P5-02 CAN Open Baud Rate
125 1000 500 kbps
Sets the baud rate when CAN Open communications are used
P5-03 Modbus RTU Baud Rate
9.6 115.2 115.2 kbps
Sets the baud rate when CAN Open communications are used
P5-04 Modbus Data Format
- - n-1 -
Sets the expected Modbus telegram data format as follows
n -1 : No Parity, 1 stop bit
n-2 : No parity, 2 stop bits
0 -1 : Odd parity, 1 stop bit
-1 : Even parity, 1 stop bit
P5-05 Communications Loss Timeout
0.0 5.0 1. 0 %
Sets the watchdog time period for the communications channel. If a valid telegram is not received by the Fenner QD:Neo
within this time period, the drive will assume a loss of communications has occurred and react as selected below
P5-06 Communication Loss Action
0 3 0 -
Controls the behaviour of the drive following a loss of communications as determined by the above parameter setting.
0: Trip & Coast To Stop
1: Ramp to Stop Then Trip
2: Ramp to Stop Only (No Trip)
3: Run at Preset Speed 8
P5-07 Fieldbus Ramp Control
0 1 0 -
Selects whether the acceleration and deceleration ramps are control directly via the Fieldbus, or by internal drive parameters
P1-03 and P1-04.
0 : Disabled. Ramps are control from internal drive parameters
1 : Enabled. Ramps are controlled directly by the Fieldbus
P5-08 Fieldbus Process Data Word 4 Output Select
0 4 0 -
When using an optional fieldbus interface, this parameter configures the parameter source for the 4th process data word
transferred from the drive to the network master during cyclic communications
0 : Output Torque – 0 to 2000 = 0 to 200.0%
1 : Output Power – Output power in kW to two decimal places, e.g. 400 = 4.00kW
2 : Digital Input Status – Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog Input 2 Signal Level – 0 to 1000 = 0 to 100.0%
4 : Drive Heatsink Temperature – 0 to 100 = 0 to 100°C
P5-09 Reserved Parameter
- - - -
No Function