10.0 Technical Data
10.1 Environmental
Ambient temperature Operational : -10...50°C (IP20 units), 40°C (IP55 units)
Storage : -40°C...60°C
Max altitude for rated operation : 1000m
Derating above 1000m (to 400m max) : 1% / 100m
Relative Humidity : <95% (non condensing)
Note: Drive must be frost and moisture free at all times. Installation above 2000m is not UL approved.
10.2 Output Power and Current Ratings
The following tables provide the output current rating infomation for the various Fenner QD:Neo models. It is also recommended that the
selection of the correct Fenner QD:Neo is based upon the motor full load current at the incoming supply voltage.
200-240 Volt (+/- 10%) 1 Phase Input, 3 Phase Output
kW HP Nominal
Input Current
Fuse or MCB (Type B) Supply Cable Size Nominal
Output
Current
Motor Cable Size Maxi-
mum
Motor
Cable
Recom-
mended
Brake
Resistance
Non UL UL mm AWG/kcmil mm AWG Length
0.75 1 10.5 16 15 2.5 12 4.3 1. 5 14 10 0 10 0
1. 5 2 16.2 20 20 4 10 7 1.5 14 100 50
2.2 3 23.8 25 25 10 8 10.5 1.5 14 100 35
NOTE:
• The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length
limit may be increased by 50%. When using the Fenner recommended output choke, the maximum cable length may be increased by 100%
• The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor
terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor.
Fenner recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life
• For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses
200-240 Volt (+/-10%) 3 Phase Input, 3 Phase Ouput
kW HP Frame
Size
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply Cable Size Nomibal
Output
Current
150%
Output
Current
60 secs
Motor Cable Size Max
Motor
Cable
Length
Optional Brake
Resistor
Min Rec
Amps Amps mm
2
AWG Amps Amps mm
2
AWG m
0.75 1 2 5.7 10 1. 5 14 4.3 6.45 1. 5 14 100 25 10 0
1. 5 2 2 8.4 10 1. 5 14 7 10.5 1. 5 14 100 25 10 0
2.2 3 2 13.1 16 2.5 12 10.5 15.75 1. 5 14 100 25 50
4 5 3 1 7. 3 25 4 10 18 27 4 12 100 20 50
5.5 7. 5 4 25 32 6 8 24 36 4 10 10 0 12 22
7. 5 10 4 46.6 50 10 6 39 57 6 8 10 0 12 22
11 15 4 54.1 63 16 4 46 69 10 6 100 12 12
15 20 5 69.6 80 25 2 61 90.5 16 4 10 0 6 6
18.5 25 5 76.9 80 25 2 72 54 16 4 100 6 6
22 30 5 92.3 10 0 35 1 90 67.5 25 2 10 0 6 6
30 40 6 116.9 125 50 2/0 110 82.5 25 1/0 10 0 3 3
37 50 6 150.2 160 70 3/0 150 112.5 35 2/0 100 3 3
45 60 6 176.5 200 90 - 180 135 50 3/0 10 0 3 3
55 75 7 2 11 250 150 - 202 151.5 150 4/0 10 0 3 3
75 10 0 7 259 315 2 x 120 - 248 180 2 x 120 - 100 3 3
90 120 7 314 400 2 x 120 - 312 225 2 x 120 - 100 3 3