LP GAS REQUIREMENTS
LP Gas Requirements
Always check the rating plate to make sure the gas supply you are hooking up to is the gas type the
firepit/fireplace is manufactured for.
IMPOR
TANT WARNING: All Cal Flame firepit/fireplaces are manufactured with the highest regard
to safety. For this reason, Cal Flame firepit/fireplaces are either
manufactured to operate on Liquid Propane (LP) or Natural Gas (NG)
and cannot be conver
ted. To verify the firepit/fireplaces operating fuel,
remove the bottom drip pan and check serial number label on the left.
Either LP or NG will be marked on the operating tab, indicating the
proper operating fuel. Attempting to convert Cal Flame firepit/fireplaces
from one fuel to another may result in serious injury and void the
warranty coverage.
NOTE
: Please note that if you do not have an updated filler valve on your existing propane tank, you will
need to purchase one at your local hardware store, as you will not be allowed to refill the tank at
any filling station.
LP Gas Hook Up
NOTE
: An enclosure for an LP gas cylinder shall be vented by openings at the level of the cylinder valve and
at floor level. The effectiveness of the opening(s) for purposes of ventilation shall be determined with
the LP-gas supply cylinder in place. This shall be accomplished in one of the following manners:
1. One side of the enclosure shall be completely open.
2. Enclosures that have four sides, complete with a top and bottom:
a. At least two ventilation openings at cylinder valve level shall be provided in the sidewall, equally sized,
spaced at 180˚ (3.14 rad), and unobstructed. Each opening shall have a total free area of not less than fi”
square inch per pound (7.1 cm≈/kg) of stored fuel capacity, and not less than a total free area of 10 square
inches (64.5 cm≈).
b. Ventilation opening(s) shall be provided at floor level and shall have a total free area of not less than fi
square inch per pound (7.1 cm≈/kg) of stored fuel capacity and not less than a total free area of 10 square
inches (64.5cm≈). If ventilation openings at floor level are in a sidewall, there shall be at least two
openings. The bottom of the openings shall be at floor level and the upper edge no more than 5 inches
(127 mm) above the floor. The openings shall be equally sized, spaced at 180˚ (3.14 rad) and
unobstructed.
c. Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2 mm)
diameter rod.
Owner’s Manual Page 7
Owner’s Manual LP Gas Requirements
Figure 1. LP Attachment Assembly
Open