Catalog 1114-1 SmartSource™ 2-Stage Horizontal & Vertical Water Source Heat Pumps GTH - Horizontal Ceiling GTV - Vertical Floor Unit Sizes 026 – 072 • R-410A Refrigerant Engineered for flexibility and performance™
Contents Model Nomenclature.......................................................... 3 AHRI Performance Data..................................................... 5 Introduction......................................................................... 6 SmartSource™ 2-Stage Horizontal & Vertical Water Source Heat Pumps........................................................................ 6 SmartSource Unique Features........................................... 7 Model GTH-Horizontal & GTV-Vertical Unit.....
Model Nomenclature Note: Text displayed in Bold-Italics designate standard offering.
Model Nomenclature Category Code Item Code Option Code Designation & Description (Bold-Italic = Standard) Desuperheater (Hot Water Generator) 25 30 D = Desuperheater Y = None Loop Pump 26 31-32 1S = One Low Head 230 Volt Pump, Grundfos UP26-99F 1L = One High Head 230 Volt Pump, Grundfos UP26-116F 2S = Two Low Head 230 Volt Pumps, Grundfos UP26-99F 2L = Two High Head 230 Volt Pumps, Grundfos UP26-116F 3S = One Low Head 115 Volt Pump, Grundfos UP26-99F 4S = Two Low Head 115 Volt Pumps,
AHRI Performance Data Rated in accordance with AHRI/ASHRAE/ISO Standard 13256-1. Unit Size Capacity Modulation Pressure Drop PSI Cooling GPM Ft CFM Total Cap. Heating EER CFM Tot Cap. COP Water Loop 026 032 038 044 049 064 072 Full load 2.5 5.7 6.5 800 26400 18.0 800 29300 5.7 Part load 2.5 5.7 6.5 700 19800 20.3 700 21800 6.4 Full load 3.3 7.4 7.5 1000 32500 16.5 1000 36400 5.3 Part load 3.3 7.4 7.5 875 24700 18.5 875 27800 6.0 Full load 2.0 4.7 9.
Introduction SmartSource™ 2-Stage Horizontal & Vertical Water Source Heat Pumps Industry Leading Efficiences, Very Quiet Operation SmartSource™ water source heat pumps from Daikin McQuay combine industryleading efficiencies with low-noise operation, high indoor air quality and consistent air temperatures. So now you can do your part to conserve energy and enjoy a quiet and comfortable indoor environment.
SmartSource Unique Features Model GTH-Horizontal & GTV-Vertical Unit Features 1. ECM Fan Motor: 4 field adjustable cfm settings and 28 programmed cfm values provide a wide range of airflow selections for quieter operation and lower energy consumption. 2. Two-Stage Compressor: available in a variety of commercial voltages, mounted on a double isolation system for reduced sound and vibration transmission. 3.
SmartSource Unique Features Four Unique Dehumidification Options: • • • • Smart Dehumidification – Uses hot gas reheat, humidistat, 2-stage thermostat & smart air flow management for precise humidity control. Simplified Dehumidification – Uses a 3-stage thermostat to optimize unit capacity and fan speed for maximum latent capacity while decreasing room humidity levels. Humidistat Controlled Dehumidification – Uses a humidistat and 2-stage thermostat to control room humidity levels.
SmartSource Unique Features Waterside Economizer The waterside economizer option helps to reduce energy consumption by using cool loop water temperatures to condition a space without energizing mechanical cooling. Even in the coldest weather a space can experience a build-up of ambient heat from people, equipment, lighting and the sun.
SmartSource Unique Features Left-hand, top discharge Right-hand, top discharge Control Box Water Connections Control Box Water Connections Front Figure 2: Four horizontal unit configurations 1. Left-hand, end discharge 2. Left-hand, straight discharge Front 3. Right-hand, end discharge Front Premium type insulation is provided standard with all SmartSource horizontal and vertical unit cabinets providing a high level of indoor air quality.
SmartSource Unique Features Field Adjustable ECM Fan Motor ECM motors are standard on all units, with 4 field-selectable CFM settings and 28 programmed CFM values. ECM motors provide the ultimate in efficiency, performance flexibility and reduced sound levels. With inherent high efficiencies compared to conventional PSC or fix speed motors, the ECM motor can save operating energy.
SmartSource Unique Features Filter & Filter Rack CorMax® Connections Units come standard with a 2" (51mm) thick factory-installed throwaway filter, mounted in a 4-sided combination filter rack and return air duct collar. Filters can be easily removed from either side by interchanging the removable filter door to the right or left side by rotating the filter rack assembly 180 degrees. A 2" or 4" filter rack is available as a factory-installed selectable option to accept a Merv 8 or Merv 13 filter.
Controls Unit Control MicroTech III SmartSourcee Unit Control & I/O Expansion Module Built-in Diagnostics The MicroTech III SmartSource Controller is a microprocessor-based control board in combination with an I/O Expansion Module for extra functionality. The control box is accessible through the left or right end corner panel on horizontal units and through the bottom-front access panel on the vertical unit.
Controls Operating Modes ■ Start-up – The unit will not operate until all the inputs and safety controls are checked for normal conditions. ■ Cooling Mode – On a call for cooling, the fan will energize at its “fan only” setting, the pump request will engergize, the 45 second flow timer will start after the flow, compressor minimum off, and random startup timers are expired, the compressor and fan will start at the stage 1 cooling settings.
Controls ■ Boilerless Electric Heat Mode – When the entering water temperature is below setpoint, the compressor will not be allowed to operate. On a call for heating, stage 1 electric heat will be energized and the fan will start at its electric heat setting. For units equipped with 2 stages of electric heat, if room setpoint conditions are not satisfied, the second stage of electric heat will be energized and the fan will continue to operate at its electric heat setting.
Controls Unit Protections & LED Fault Status Annunciation Refrigerant Circuit High Pressure Protection A normally closed high (compressor discharge) pressure switch is used in SmartSource units to help protect the refrigerant circuit from excessively high pressure. The controller will monitor this switch. Note: Due to the method of sensing the HP switch, the true state cannot be determined unless the compressor output is active.
Controls Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset automatic lockouts. There are (3) means to reset an automatic lockout condition: • Using the thermostat create 2 demands for capacity within 30 seconds.
Controls Table 5: Priority Level of Faults and Modes Priority Level Mode or Fault 1 I/O Expansion Communication Fail 2 Invalid Configuration 3 Low Voltage Brownout 4 Emergency Shutdown Mode 5 Compressor High Pressure 6 Compressor Low Pressure 7 Compressor Suction Temp Sensor Fail 8 Compressor Low Suction Temp 9 Freeze Fault 10 Room Temp Sensor Fail 11 Entering Water Temp Sensor Fail 12 Leaving Water Temp Sensor Fail 13 Condensate Overflow 14 Low Entering Water Temp 15 Serial E
Controls MicroTech III SmartSource Unit Controller with BACnet Communication Module Daikin McQuay water source heat pumps are available with a BACnet MS/TP communication module that is designed to communicate over a BACnet MS/TP communications network to a building automation system (BAS). It can be factory or field-installed. The unit controller is programmed and tested with all the logic required to monitor and control the unit.
Accessories Hoses, Hose Kits and Shutoff Ball Valves for SmartSource Water Source Heat Pumps Daikin McQuay sells a variety of flexible supply, return and condensate hoses and hose assemblies for connecting its water source heat pumps to a building's hard piping system. Both standard and fire-rated hoses are available. Figure 8: Flexible, steel braided supply and return hoses Supply and return hoses have a swivel fitting at one end to facilitate removal of the unit for replacement or service.
Accessories Supply Hose Construction Body: Brass C37000 Ball: Full Port Chrome Plated Ball Stem: Teflon® Stem: Explosion Proof O-Rings: EPDM Strainer: 20 Mesh Stainless Steel Bypass Port Tap: • 1/2" NPTF for sizes 1/2", 3/4" and 1" • 3/4" NPTF for sizes 1-1/4", 1-1/2" Maximum Working Pressure: 400 psig Maximum Operating Temp: -4°F to 250°F Table 9: Available hose kits Description Connection Size (O.D.) Length 0.5 1.0 1.5 2.0 2.5 1/2" 3.0 3.5 4.0 4.5 5.
Accessories Condensate Hose Kits Table 11: Available electric duct heaters Description kW Voltage/Hz/Phase Unit Size 208-240/60/1 5 208-240/60/3 277/60/1 480/60/3 208-240/60/1 10 Horizontal ceiling units require an external condensate hose. These can be ordered as the long clear plastic type with the necessary clamps and a MPT hose fittings, or fire rated type for connection to the FPT field piping.
Accessories Thermostats Daikin-McQuay has a line of thermostats and thermostat accessories to serve the SmartSource line of water source heat pumps. Programmable and Non-Programmable Thermostats Programmable Touch Screen for Smart Dehumidification or Waterside Economizer Control With advanced capabilities to control Smart Dehumidification or the Waterside Economizer, the Programmable Touch Screen thermostat offers precise temperature and humidity sensing and control.
Accessories Digitally Adjustable Sensor with Temperature and Humidity Display Specifically designed for Smart Dehumidification or Waterside Economizer applications, the Digitally Adjustable sensor provides the ultimate of temperature and humidity control and display, simple user interface, alarm annunciation, and alarm reset.
Accessories Remote Sensors for Thermostat Applications Thermostats Programmable Touch-screen NonProgrammable Programmable Thermostats & Remote Sensors used with GT 2-Stage Units Part No. 910121750 Part No. 910121746 Part No. 910121748 Remote Room Sensor Remote Room Sensor Outdoor Air Sensor Used with Thermostats 910121746 & 910121748 Used with Thermostat 910121750 Used with Thermostat 910121750 Part No. 667720401 Part No. 910129095 Part No.
Accessories Room Temperature Sensors Adjustable Cool/ Warm with Occupancy Switch Adjustable 55°F to 95°F Adjustable +/- 3ºF or +/-1.5°C Basic Sensor Part No. 910121754 Part No. 910121753 Part No. 669529101 Part No. 669529201 Part No. 669529001 Digitally Adjustable Cool to Warm 55ºF to 95ºF (13º to 35ºC) -3º to +3ºF (-1.5º to +1.
Applications Typical Vertical Installation Unit Location SmartSource vertical water source heat pumps can be installed “free standing” in an equipment room; however, closet installations are more common for the small vertical type units. Generally, the unit is located in the corner of a closet with the non-ducted return air facing 90º to the door and the major access panels facing the door as shown in Figure 13.
Applications Typical Horizontal Installation Unit Location It is important to leave enough space for service personnel to perform maintenance or repair. Locate the horizontal unit to allow for easy removal of the filter and access panels. Allow a minimum of 18" (46 cm) clearance on each side of the unit for service and maintenance access and do not install the unit above any piping.
Applications Figure 17: Vertical unit duct example Acoustically Insulated Duct (approximately 10') 90° elbow Room Air Supply Diffuser Trunk Duct Flexible (Boot) Connector Trunk Duct Tee Branch Duct Room Air Supply Diffuser Branch Duct Room Air Supply Diffuser Figure 18: Horizontal unit duct example Acoustically Insulated Return Air Duct Room Air Supply Diffuser Trunk Duct Flexible (Boot) Connector Acoustically Insulated Duct (approximately 10') Trunk Duct Tee Branch Duct Branch Duct Room Air S
Applications Piping The water source heat pump unit is typically connected to the supply / return piping using a “reverse return” piping system which includes a flow control device so that flow requirements are met for each zone. A short, high pressure “flexible hose” is used to connect the unit to the building’s hard piping and acts as a sound attenuator for both the unit operating noise and hydronic pumping noise.
Applications Water System Quality The cleaning, flushing and chemical treatment of a water source heat pump system is fundamental to efficient operation and the life expectancy of the system. Potential system problems produced by the use of water fall into three general categories: 1. Scale formation – Mineral deposits which result from the crystallization and precipitation of dissolved salts in the water.
Applications Condensate Drain Improper trapping can lead to several problems. If the trap is too tall, negative pressure will prevent drainage, causing condensate backup. If the trap is too short the seal will be destroyed or nonexistent, producing the same effect as a non-trapped system. Construct the trap of 7/8" clear plastic piping. The condensate piping from the drain trap must be sloped to facilitate proper drainage. The clear plastic trap should be clamped and removable for cleaning.
Applications Unit Selection Achieving optimal performance with water source heat pump systems requires both accurate system design and proper equipment selection. Use a building load program to determine the heating and cooling loads of each zone prior to making equipment selections. With this information, the Daikin McQuay SelectTools™ software selection program for Water Source Heat Pumps can be used to provide fast, accurate and complete selections of all water source heat pump products.
Applications Zone Requirement: Total Cooling Zone = 41,099 BTUH Sensible Cooling Zone = 30,327 BTUH Heating Zone = 37,758 BTUH Design Air Flow = 1,200 CFM Return air – Cooling = 80°F DB/67°F WB Return air – Heating = 70°F Entering Fluid Temperature Cooling = 100°F – 20% P.G. Entering Fluid Temperature Heating = 45°F – 20% P.G. A Model GT *044 is chosen for this geothermal application.
Applications When selecting an appropriate SmartSource loop pump, the working fluid (water plus antifreeze), total head loss and flow must be known. The following represents the typical total head loss calculation for a decentralized geothermal loop pump application: ■ Using nominal 2-ton vertical unit W.GTV.1.026 ■ Fluid – 15% Methanol Solution in Water ■ Design EWT Heating - 35°F (Maximum pressure drop occurs with high density fluid.
Capacity Data – Size 026 (800 CFM) EWT (°F) GPM 4.0 20 6.0 8.0 4.0 30 6.0 8.0 4.0 40 6.0 8.0 4.0 50 6.0 8.0 4.0 60 6.0 8.0 Page 36 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 1.2 1.2 1.2 1.2 1.2 2.5 2.5 2.5 2.5 2.5 4.2 4.2 4.2 4.2 4.2 1.2 1.2 1.2 1.2 1.2 2.4 2.4 2.4 2.4 2.4 2.7 2.7 2.7 2.7 2.7 5.7 5.7 5.7 5.7 5.7 9.6 9.6 9.6 9.6 9.6 2.7 2.7 2.7 2.7 2.7 5.5 5.5 5.5 5.5 5.
Capacity Data – Size 026 (800 CFM) EWT (°F) GPM 4.0 70 6.0 8.0 4.0 80 6.0 8.0 4.0 90 6.0 8.0 4.0 100 6.0 8.0 4.0 110 6.0 8.0 Catalog 1114-1 WPD Cooling Heating EAT (°F) Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) THR (Btu/hr) EER PSI FT of W.C. 1.0 1.0 1.0 1.0 1.0 2.2 2.2 2.2 2.2 2.2 3.7 3.7 3.7 3.7 3.7 1.0 1.0 1.0 1.0 1.0 2.1 2.1 2.1 2.1 2.1 2.4 2.4 2.4 2.4 2.4 5.0 5.0 5.0 5.0 5.0 8.4 8.4 8.4 8.4 8.4 2.3 2.3 2.3 2.3 2.3 4.9 4.9 4.9 4.9 4.
Capacity Data – Size 032 (1000 CFM) EWT (°F) GPM 5.0 20 7.5 10.0 5.0 30 7.5 10.0 5.0 40 7.5 10.0 5.0 50 7.5 10.0 5.0 60 7.5 10.0 Page 38 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 1.8 1.8 1.8 1.8 1.8 3.7 3.7 3.7 3.7 3.7 6.3 6.3 6.3 6.3 6.3 1.7 1.7 1.7 1.7 1.7 3.6 3.6 3.6 3.6 3.6 4.1 4.1 4.1 4.1 4.1 8.5 8.5 8.5 8.5 8.5 14.4 14.4 14.4 14.4 14.4 4.0 4.0 4.0 4.0 4.0 8.3 8.3 8.3 8.3 8.
Capacity Data – Size 032 (1000 CFM) EWT (°F) GPM 5.0 70 7.5 10.0 5.0 80 7.5 10.0 5.0 90 7.5 10.0 5.0 100 7.5 10.0 5.0 110 7.5 10.0 Catalog 1114-1 WPD PSI FT of W.C. 1.6 1.6 1.6 1.6 1.6 3.3 3.3 3.3 3.3 3.3 5.5 5.5 5.5 5.5 5.5 1.5 1.5 1.5 1.5 1.5 3.2 3.2 3.2 3.2 3.2 5.4 5.4 5.4 5.4 5.4 1.5 1.5 1.5 1.5 1.5 3.2 3.2 3.2 3.2 3.2 5.3 5.3 5.3 5.3 5.3 1.5 1.5 1.5 1.5 1.5 3.1 3.1 3.1 3.1 3.1 5.2 5.2 5.2 5.2 5.2 1.5 1.5 1.5 1.5 1.5 3.1 3.1 3.1 3.1 3.1 5.2 5.2 5.2 5.2 5.2 3.6 3.6 3.6 3.6 3.
Capacity Data – Size 038 (1250 CFM) EWT (°F) GPM 6.0 20 9.0 12.0 6.0 30 9.0 12.0 6.0 40 9.0 12.0 6.0 50 9.0 12.0 6.0 60 9.0 12.0 Page 40 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 2.1 2.1 2.1 2.1 2.1 4.4 4.4 4.4 4.4 4.4 7.4 7.4 7.4 7.4 7.4 2.0 2.0 2.0 2.0 2.0 4.3 4.3 4.3 4.3 4.3 4.8 4.8 4.8 4.8 4.8 10.1 10.1 10.1 10.1 10.1 17.0 17.0 17.0 17.0 17.0 4.7 4.7 4.7 4.7 4.7 9.8 9.8 9.8 9.8 9.
Capacity Data – Size 038 (1250 CFM) EWT (°F) GPM 6.0 70 9.0 12.0 6.0 80 9.0 12.0 6.0 90 9.0 12.0 6.0 100 9.0 12.0 6.0 110 9.0 12.0 Catalog 1114-1 WPD PSI FT of W.C. 1.8 1.8 1.8 1.8 1.8 3.9 3.9 3.9 3.9 3.9 6.5 6.5 6.5 6.5 6.5 1.8 1.8 1.8 1.8 1.8 3.8 3.8 3.8 3.8 3.8 6.4 6.4 6.4 6.4 6.4 1.8 1.8 1.8 1.8 1.8 3.7 3.7 3.7 3.7 3.7 6.3 6.3 6.3 6.3 6.3 1.8 1.8 1.8 1.8 1.8 3.7 3.7 3.7 3.7 3.7 6.2 6.2 6.2 6.2 6.2 1.7 1.7 1.7 1.7 1.7 3.6 3.6 3.6 3.6 3.6 6.1 6.1 6.1 6.1 6.1 4.2 4.2 4.2 4.2 4.
Capacity Data – Size 044 (1400 CFM) EWT (°F) GPM 7.0 20 10.5 14.0 7.0 30 10.5 14.0 7.0 40 10.5 14.0 7.0 50 10.5 14.0 7.0 60 10.5 14.0 Page 42 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 1.1 1.1 1.1 1.1 1.1 2.3 2.3 2.3 2.3 2.3 4.0 4.0 4.0 4.0 4.0 1.1 1.1 1.1 1.1 1.1 2.3 2.3 2.3 2.3 2.3 2.5 2.5 2.5 2.5 2.5 5.4 5.4 5.4 5.4 5.4 9.2 9.2 9.2 9.2 9.2 2.4 2.4 2.4 2.4 2.4 5.2 5.2 5.2 5.2 5.
Capacity Data – Size 044 (1400 CFM) EWT (°F) GPM 7.0 70 10.5 14.0 7.0 80 10.5 14.0 7.0 90 10.5 14.0 7.0 100 10.5 14.0 7.0 110 10.5 14.0 Catalog 1114-1 WPD PSI FT of W.C. 1.0 1.0 1.0 1.0 1.0 2.1 2.1 2.1 2.1 2.1 3.5 3.5 3.5 3.5 3.5 0.9 0.9 0.9 0.9 0.9 2.0 2.0 2.0 2.0 2.0 3.4 3.4 3.4 3.4 3.4 0.9 0.9 0.9 0.9 0.9 2.0 2.0 2.0 2.0 2.0 3.4 3.4 3.4 3.4 3.4 0.9 0.9 0.9 0.9 0.9 2.0 2.0 2.0 2.0 2.0 3.3 3.3 3.3 3.3 3.3 0.9 0.9 0.9 0.9 0.9 1.9 1.9 1.9 1.9 1.9 3.3 3.3 3.3 3.3 3.3 2.2 2.2 2.2 2.
Capacity Data – Size 049 (1600 CFM) EWT (°F) GPM 8.0 20 12.0 16.0 8.0 30 12.0 16.0 8.0 40 12.0 16.0 8.0 50 12.0 16.0 8.0 60 12.0 16.0 Page 44 of 76 WPD PSI FT of W.C. 1.4 1.4 1.4 1.4 1.4 3.0 3.0 3.0 3.0 3.0 5.1 5.1 5.1 5.1 5.1 1.4 1.4 1.4 1.4 1.4 2.9 2.9 2.9 2.9 2.9 5.0 5.0 5.0 5.0 5.0 1.3 1.3 1.3 1.3 1.3 2.8 2.8 2.8 2.8 2.8 4.8 4.8 4.8 4.8 4.8 1.3 1.3 1.3 1.3 1.3 2.8 2.8 2.8 2.8 2.8 4.7 4.7 4.7 4.7 4.7 1.3 1.3 1.3 1.3 1.3 2.7 2.7 2.7 2.7 2.7 4.6 4.6 4.6 4.6 4.6 3.2 3.2 3.2 3.2 3.
Capacity Data – Size 049 (1600 CFM) EWT (°F) GPM 8.0 70 12.0 16.0 8.0 80 12.0 16.0 8.0 90 12.0 16.0 8.0 100 12.0 16.0 8.0 110 12.0 16.0 Catalog 1114-1 WPD PSI FT of W.C. 1.2 1.2 1.2 1.2 1.2 2.6 2.6 2.6 2.6 2.6 4.5 4.5 4.5 4.5 4.5 1.2 1.2 1.2 1.2 1.2 2.6 2.6 2.6 2.6 2.6 4.4 4.4 4.4 4.4 4.4 1.2 1.2 1.2 1.2 1.2 2.5 2.5 2.5 2.5 2.5 4.3 4.3 4.3 4.3 4.3 1.2 1.2 1.2 1.2 1.2 2.5 2.5 2.5 2.5 2.5 4.3 4.3 4.3 4.3 4.3 1.2 1.2 1.2 1.2 1.2 2.5 2.5 2.5 2.5 2.5 4.2 4.2 4.2 4.2 4.2 2.8 2.8 2.8 2.
Capacity Data – Size 064 (2000 CFM) EWT (°F) GPM 10.0 20 15.0 20.0 10.0 30 15.0 20.0 10.0 40 15.0 20.0 10.0 50 15.0 20.0 10.0 60 15.0 20.0 Page 46 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 2.2 2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9 4.9 8.4 8.4 8.4 8.4 8.4 2.2 2.2 2.2 2.2 2.2 4.7 4.7 4.7 4.7 4.7 5.1 5.1 5.1 5.1 5.1 11.1 11.1 11.1 11.1 11.1 19.2 19.2 19.2 19.2 19.2 4.9 4.9 4.9 4.9 4.9 10.7 10.7 10.7 10.7 10.
Capacity Data – Size 064 (2000 CFM) EWT (°F) GPM 10.0 70 15.0 20.0 10.0 80 15.0 20.0 10.0 90 15.0 20.0 10.0 100 15.0 20.0 10.0 110 15.0 20.0 Catalog 1114-1 WPD PSI FT of W.C. 2.0 2.0 2.0 2.0 2.0 4.2 4.2 4.2 4.2 4.2 7.3 7.3 7.3 7.3 7.3 1.9 1.9 1.9 1.9 1.9 4.2 4.2 4.2 4.2 4.2 7.2 7.2 7.2 7.2 7.2 1.9 1.9 1.9 1.9 1.9 4.1 4.1 4.1 4.1 4.1 7.1 7.1 7.1 7.1 7.1 1.9 1.9 1.9 1.9 1.9 4.0 4.0 4.0 4.0 4.0 7.0 7.0 7.0 7.0 7.0 1.8 1.8 1.8 1.8 1.8 4.0 4.0 4.0 4.0 4.0 6.9 6.9 6.9 6.9 6.9 4.5 4.5 4.
Capacity Data – Size 072 (2160 CFM) EWT (°F) GPM 12.0 20 18.0 24.0 12.0 30 18.0 24.0 12.0 40 18.0 24.0 12.0 50 18.0 24.0 12.0 60 18.0 24.0 Page 48 of 76 WPD EAT (°F) Cooling Total (Btu/hr) Sensible (Btu/hr) Power Input (kW) Heating THR (Btu/hr) PSI FT of W.C. 3.2 3.2 3.2 3.2 3.2 6.9 6.9 6.9 6.9 6.9 11.9 11.9 11.9 11.9 11.9 3.1 3.1 3.1 3.1 3.1 6.7 6.7 6.7 6.7 6.7 7.2 7.2 7.2 7.2 7.2 15.7 15.7 15.7 15.7 15.7 27.1 27.1 27.1 27.1 27.1 7.0 7.0 7.0 7.0 7.0 15.2 15.2 15.2 15.2 15.
Capacity Data – Size 072 (2160 CFM) EWT (°F) GPM 12.0 70 18.0 24.0 12.0 80 18.0 24.0 12.0 90 18.0 24.0 12.0 100 18.0 24.0 12.0 110 18.0 24.0 Catalog 1114-1 WPD PSI FT of W.C. 2.8 2.8 2.8 2.8 2.8 6.0 6.0 6.0 6.0 6.0 10.4 10.4 10.4 10.4 10.4 2.7 2.7 2.7 2.7 2.7 5.9 5.9 5.9 5.9 5.9 10.2 10.2 10.2 10.2 10.2 2.7 2.7 2.7 2.7 2.7 5.8 5.8 5.8 5.8 5.8 10.0 10.0 10.0 10.0 10.0 2.6 2.6 2.6 2.6 2.6 5.7 5.7 5.7 5.7 5.7 9.9 9.9 9.9 9.9 9.9 2.6 2.6 2.6 2.6 2.6 5.7 5.7 5.7 5.7 5.7 9.8 9.8 9.8 9.
Performance Data Fan Performance Table 16: 2-Stage units with constant cfm type ECM motor Unit Size 026 032 038 044 049 064 072 Note: Setting Maximum ESP (in. wg.) Part Load Stage 1 Heat Full Load Stage 2 Heat Part Load Stage 1 Cool Full Load Stage 2 Cool Fan Only Dehumidification Electric Heat Setting 4 (High) .70 800 900 800 900 600 600 900 Setting 3 (Standard) .70 700 800 700 800 600 600 900 Setting 2 (Medium) .70 600 700 600 700 450 600 900 Setting 1 (Low) .
Performance Data Air Flow Correction Factors – Full Load Table 17: Air flow correction factors (full load) – sizes 026-072 Unit Size Air Flow Setting Cooling Total Capacity Sensible Capacity Heating Power Input Total Capacity Power Input Setting 4 (High) 1.013 1.070 1.016 1.009 0.996 Setting 3 (Standard) 1.000 1.000 1.000 1.000 1.000 026 Setting 2 (Medium) 0.987 0.938 0.985 0.992 1.004 Setting 1 (Low) 0.975 0.884 0.970 0.983 1.008 Setting 4 (High) 1.018 1.091 1.028 1.
Performance Data Air Flow Correction Factors – Part Load Table 18: Air flow correction factors (part load) – sizes 026-072 Unit Size Air Flow Setting Setting 4 (High) Cooling Heating Total Capacity Sensible Capacity Power Input Total Capacity Power Input 1.011 1.080 1.017 1.005 0.991 Setting 3 (Standard) 1.000 1.000 1.000 1.000 1.000 Setting 2 (Medium) 0.989 0.931 0.984 0.995 1.009 Setting 1 (Low) 0.989 0.931 0.984 0.995 1.009 026 Setting 4 (High) 1.010 1.046 1.015 1.
Performance Data Desuperheater Performance Table 19: Desuperheater Cooling Mode Unit Ton Desuperheater GPM Desuperheater EWT °F 026 0.8 90 1.0 032 036 2,300 32 2,200 2,875 70 3,520 77 2,875 32 2,750 90 3,594 70 4,400 77 3,450 32 3,300 90 4,313 70 5,280 77 4,025 32 3,850 90 5,031 70 6,160 77 4,600 32 4,400 90 2.0 072 77 90 90 1.6 064 Desuperheater Capacity Btu/hr. Unit EWT °F 90 1.4 049 Unit EWT °F 90 1.
Performance Data Table 22: 1600 to 2400 CFM1 CFM Unit Size GPM 1600 Total 044, 049 2 2 Notes: Sensible Total 2000 Sensible Total 2200 Sensible Total 2400 Sensible Total Sensible 3 WPD ft. of wc. 8 44.9 37.1 46.9 39.8 1.53 10 49.2 39.0 51.6 42.1 2.43 12 52.8 40.6 55.3 43.7 3.46 PD (" wc.) 064, 072 1800 0.177 0.211 12.5 56.5 42.5 59.5 46.0 62.2 49.3 64.6 52.4 66.8 55.3 2.67 15 60.1 43.9 63.5 47.8 66.4 51.2 69.1 54.4 71.6 57.5 3.79 18 63.5 45.
Electrical Data Table 25: Standard unit without options Unit Size 026 032 Rated Voltage Voltage Maximum Fuse or HACR Breaker Size 11.7 58.3 3.0 14.7 17.6 25 9.1 54.0 2.6 11.7 14.0 20 208-230/60/3 197 6.5 55.4 3.0 9.5 11.1 15 *460/60/3 414 3.5 28.0 2.6 6.1 7.0 15 208-230/60/1 197 239 197 414 197 197 414 197 197 414 197 197 414 197 197 414 197 197 414 13.1 73.0 5.0 18.1 21.4 30 10.2 60.0 4.1 14.3 16.9 25 8.7 58.0 5.0 13.7 15.9 20 4.3 28.0 4.1 8.4 9.
Correction Factors Motorized 2-Way Water Valve Formula: QL 2 ∆P = SL Water Pressure Drop Adders Cv Cv MOPD Unit Size GPM PSI Ft of H2O Where: 4.0 0.15 0.35 Cv – Valve (Flow) coefficient for valves 026 10.3 150 6.0 0.34 0.78 8.0 0.60 1.39 QL – Liquid flow in gallons per minute (GPM) 5.0 0.24 0.54 Qg – Rate of gas flow in cubic feet per minute at 032 10.3 150 7.5 0.53 1.22 standard conditions, 14.7 PSIA and 60ºF 10.0 0.94 2.17 6.0 0.45 1.05 (SCFM) 036 8.9 150 9.0 1.02 2.
Physical Data Vertical Units Table 29: Unit sizes 026 through 072 Unit Size Description 026 032 038 044 049 064 072 85 120 122 Scroll Compressor Type Refrigeration Charge (Oz.) 56 56 Fan Wheel (D x W) 77 94 9" x 7" Fan Motor HP 11" x 10" 1/3 1/2 Water Connection Size (FPT) 3/4 1 3/4" 1" Desuperheater Connection Size (FPT) 1/2" Coax & Water Piping Volume (Gal. @ 70ºF) 0.5 1.1 Air Coil Face Area (Sq Ft.) 4.1 4.9 Air Coil Dimensions (H x W) 28" x 21.
Dimensional Data Horizontal Unit Left-Hand Return Front Line Voltage (Note 4) Low Voltage (Note 3) Front Right-Hand Return F C AP E L K D J H Straight Discharge A 3/4" FPT Front View Condensate Drain Connection End Discharge Choose either straight discharge or end discharge Straight Discharge 3/4" FPT Condensate Drain Connection End Discharge Choose either straight discharge or end discharge Unit Hanger Bracket Details P P FM AP C O Y X FM AP O C R R G Q G W A Q A Right Retu
Dimensional Data Table 33: Piping connections dimensions Electrical Connections in inches (mm) Piping Connections in inches (mm) GTH Horizontal Unit E D 026, 0321 1 J K L Low Voltage3 Between Line Voltage4 G F Condensate Drain 3/4" FPT H Supply Return 2.58 (66) 13.39 (340) 1.57 (40) 4.29 (109) 1.94 (49) 2.57 (65) 7.36 (187) 9.93 (252) 038 2.76 (70) 13.57 (345) 1.57 (40) 4.36 (111) 1.94 (49) 3.57 (91) 8.23 (209) 11.81 (300) 044, 0492 3.07 (78) 13.88 (353) 1.57 (40) 4.
Dimensional Data Vertical Unit B P N N P FM AP O O Front A Q M C AP Top View - Right Return Top View - Left Return 3/4 View - Right Hand Return Unit Front S R R U U T T S 1.5" (38) FM AP 1.5" (38) 1.
Dimensional Data Table 38: Piping & electrical connections dimensions Electrical Connections in inches (mm) Piping Connections in inches (mm) GTV Vertical Unit 026, 0321 038 1 D E F Supply Desuperheater Water Supply Desuperheater Water Return Return 2.58 (66) 6.68 (170) 9.68 (246) 13.39 (340) 17.39 (442) G K L Between Line Voltage4 2.45 (62) 8.63 (219) 11.07 (281) H J Condensate Low Voltage3 Drain 3/4" 3.26 (83) 7.07 (180) 10.07 (256) 14.07 (357) 17.88 (454) 2.82 (72) 9.
Engineering Guide Specifications Horizontal Unit General Units shall be supplied completely factory assembled, piped, internally wired, fully charged with R-410A and capable of operation with an entering water temperature range from 55°F to 110°F on water loop models, 30°F to 110°F on geothermal ground loop and ground water models.
Engineering Guide Specifications Refrigerant Circuit Units shall have a sealed refrigerant circuit, which includes a non-CFC depleting R-410A refrigerant [rotary (sizes 007-019), and scroll compressor (sizes 024 to 070)]. In addition, each unit will have a thermostatic expansion valve, an aluminum fin and rifled copper tube refrigerant-to-air heat exchanger, a reversing valve and a water-to-refrigerant coaxial heat exchanger.
Engineering Guide Specifications The unit mounted control system shall allow economizer operation for either supplemental to mechanical unit cooling or independent, based on entering fluid temperature and refrigerant suction temperature operating conditions. Economizer operation shall be permitted when entering fluid temperature is below 55°F yet adjustable between 70°F to 50°F. Economizer operation shall be initiated from a 3-stage wall mounted thermostat or room temperature sensor.
Engineering Guide Specifications Solid-State Control System MicroTech III SmartSource Control System - Unit shall have a microprocessor- based control system. The unit control logic shall provide cooling, heating, smart dehumidification, and/or economizer operation as required by the thermostat and/ or sensor. The control system shall provide the following for stand-alone operation: 1. The use of standard non-programmable or programmable wall thermostats. 2.
Engineering Guide Specifications Unit mounted LED annunciators aid in diagnosing unit operation by indicating the water source heat pump operating mode and alarm conditions. If there are no current alarm conditions, a green LED on the annunciator board will indicate occupied unit operating mode. If an alarm condition exists, the MicroTech III SmartSource unit controller will send the fault condition to the LED annunciator, which will assist in troubleshooting the unit.
Engineering Guide Specifications Valve Options • Optional 2-way, Normally Open (N.O.) or Normally Closed (N.C.) motorized valves. • Optional 2-way, mechanical ball valve Automatic Flow Hose Kit The automatic flow hose kit shall include an automatic flow control valve, two ball valves, two flexible hoses, a high flow Y-strainer, and may include a strainer blow-down and various other accessories.
Engineering Guide Specifications Units shall have a factory-installed, 4-sided, 1" duct flange on the discharge of the blower to allow connection of field ductwork and must have a minimum of two access panels, one for the compressor compartment and one for the blower compartment. Unit shall have an insulated panel separating the blower compartment from the compressor compartment.
Engineering Guide Specifications Hot Gas Reheat Smart Dehumidification Option The optional factory-installed hot gas reheat coil shall be used as part of a dehumidification operating sequence. Hot gas reheat shall be enabled when the space humidity level is above a user selectable set point, typically, 50 to 55% RH. Superheated refrigerant gas shall be diverted to the reheat coil and unit fan shall operate at dehumidification fan speed upon a call for dehumidification.
Engineering Guide Specifications Disconnect Switch This factory-installed option shall include the addition of a 2 or 3-pole switch mounted inside the unit and the knob or handle protruding through the corner post. The switch shall have a lockout/tag out feature. The switch shall be rated to be added to all units to handle the unit only (not to include additional amperage from field installed accessories). The switch shall be rated to handle all the voltages available for the unit.
Engineering Guide Specifications MicroTech™ III Control with LonWorks communication module – Unit shall have a microprocessor-based control system. The unit control logic shall communicate over a LonMark communications network. The unit controller is factory programmed [LonMark ® 3.4 certified Application Code the current standard for new applications] and tested with all the logic required to monitor and control heating and cooling operation.
Engineering Guide Specifications Wall Mounted Room Temperature Sensors: • Digitally Adjustable Wall Sensor with Temperature and Humidity Display • Adjustable Cool/Warm with Occupancy Switch, Override/Reset Button, Status LED, Fan and System Switch • Adjustable 55° to 95°F and 12° to 33°C, Override/Reset Button, Status LED, Fan and System Switch • Adjustable -5°F to +5°F and -20°C to -15°C, Override/Reset Button, Status LED, Fan and System Switch • Basic Sensor, Override/Reset Button, Status LED Humidistat T
This page left blank intentionally
This page left blank intentionally
This page left blank intentionally
Daikin McQuay Water Source Heat Pumps A Complete Line of Quality Products, Flexible Configurations Stacking Units 3/4 to 3 Ton Large Vertical Units 6 to 25 Ton & Horizontal Units 6 to 10 Ton Rooftop Units 3 to 35 Ton Water to Water Source Heat Pump Units 3 to 35 Ton Console Units 3/4 to 11/2 Ton Enfinity Vertical & Horizontal Units 1/2 to 6 Ton SmartSource Vertical & Horizontal Units 2 to 6 Ton SmartSource Inverter Units 3 to 4 Ton Daikin McQuay Training and Development Now that you have made an inv