Specifications
13
OPERATION OF CRYO-CYL 80 HP
52
CAUTION: The liquid and vent valves on an empty
liquid cylinder should always be kept closed to pro-
tect the inner vessel and plumbing from being
c
ontaminated.
Service and Maintenance
Refer to section 15 and 16 of this manual to trouble
shoot problems and service these liquid cylinders.
5. Open the gas use valve (Item 198).
6
. Adjust the final line regulator for the proper delivery
pressure.
7. When the gas delivery is completed, close all
liquid cylinder valves.
RELIEF VALVE ARGON NITROGEN OXYGEN CO
2
N
2
O
Setting (PSIG) LBS SCF LBS SCF LBS SCF LBS SCF LBS SCF
CRYO-CYL 80 HP (350 psig max. RV)
Gross Cap = 85 Liters
0 to 45 248 2398 142 1960 201 2427 - - - -
46 to 75 243 2350 138 1904 196 2367 - - - -
76 to 105 237 2292 134 1849 192 2318 201 1756 194 1695
106 to 170 228 2204 130 1794 187 2258 196 1713 188 1643
171 to 230 222 2146 129 1780 183 2210 194 1695 185 1616
231 to 295 215 2079 127 1752 179 2161 190 1660 181 1581
**296 to 360 211 2040 121 1670 173 2089 187 1634 177 1546
RELIEF VALVE
ARGON
NITROGEN
OXYGEN CO
2
N
2
O
Setting (BAR)
KG NM
3
KG
NM
3
KG
NM
3
KG
NM
3
KG
NM
3
CRYO-CYL 80 HP (24.1 bar max. RV)
Gross Cap = 85 Liters
0 to 3.1 112 63 64 51 94 66 - - - -
3.2 to 5.1
110
62
63
50
89 62 - - - -
5.2 to 7.2 107 60 61 49 87 61 91 46 88 44
7.3 to 11.7 103 58 59 47 85 59 89 45 85 43
11.8 to 15.9 101 57 58 46 83 58 88 44 84 42
16.0 to 20.3
98 55 58 46 81 57 86 43 82 41
**20.4 to 24.8 96 54 55 44 78 55 85 43 80 40
STANDARD FILLING WEIGHT TABLE
METRIC FILLING WEIGHT TABLE
Note:
Filling weights are shown as the maximum weight allowed by code. Their related volumes may vary with product density.
* * Normal Factory Setting