Specifications

Page 4
BLOWER DATA
GCS241353 BLOWER PERFORMANCE
STATIC PRESSURE EXTERNAL TO UNIT  Inches Water Gauge (Pa)
r
Volume
.20 (50) .40 (75) .50 (125) .70 (175) .80 (200) .90 (225) 1.00 (250) 1.10 (275) 1.30 (325) 1.50 (375)
cfm
(L/s)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
3600
(1700)
       
1.14
672
(0.85)
1.24
707
(0.93)
1.47
772
(1.10)
1.60
802
(1.19)
1.74
831
(1.30)
1.87
860
(1.40)
2.00
887
(1.49)
2.30
940
(1.72)
2.60
985
(1.94)
3800
(1795)
       
1.27
690
(0.95)
1.39
725
(1.04)
1.64
790
(1.22)
1.78
820
(1.33)
1.93
850
(1.44)
2.06
878
(1.54)
2.20
905
(1.64)
2.46
950
(1.84)
2.76
994
(2.06)
4000
(1890)
1.18
642
(0.88)
1.43
715
(1.07)
1.54
746
(1.15)
1.81
809
(1.35)
1.95
838
(1.45)
2.09
866
(1.56)
2.24
895
(1.67)
2.38
920
(1.78)
2.66
968
(1.98)
2.96
1013
(2.21)
4200
(1980)
1.35
670
(1.01)
1.50
736
(1.12)
1.73
768
(1.29)
2.00
828
(1.49)
2.13
856
(1.59)
2.28
885
(1.70)
2.43
913
(1.81)
2.56
938
(1.91)
2.86
984
(2.13)
3.19
1030
(2.38)
4400
(2075)
1.52
693
(1.13)
1.79
760
(1.34)
1.93
790
(1.44)
2.29
850
(1.71)
2.36
878
(1.76)
2.50
905
(1.87)
2.63
930
(1.96)
2.77
955
(2.07)
3.08
1003
(2.30)
       
4600
(2170)
1.70
718
(1.27)
2.00
785
(1.49)
2.15
815
(1.60)
2.44
872
(1.82)
2.59
900
(1.93)
2.71
923
(2.02)
2.84
948
(2.12)
3.00
974
(2.24)
3.32
1021
(2.48)
       
4800
(2265)
1.93
747
(1.44)
2.22
807
(1.66)
2.37
835
(1.60)
2.66
892
(1.98)
2.82
918
(2.10)
2.93
940
(2.19)
3.09
970
(2.31)
3.25
995
(2.42)
               
5000
(2360)
2.16
772
(1.61)
2.46
830
(1.84)
2.66
860
(2.06)
2.92
915
(2.18)
3.07
940
(2.29)
3.24
965
(2.42)
3.43
989
(2.56)
                       
5200
(2455)
2.41
800
(1.80)
2.75
860
(2.05)
2.89
887
(2.16)
3.22
940
(2.40)
3.42
965
(2.55)
                                       
NOTE  All data is measured external to the unit with dry coil and with the air filters in place. See Page 5 for Accessory Air Resistance data.
NOTE  In Canada, maximum usable motor output is 3 hp (2.24 kW).
GCS241603 BLOWER PERFORMANCE
STATIC PRESSURE EXTERNAL TO UNIT  Inches Water Gauge (Pa)
r
Volume
.20 (50) .40 (75) .50 (125) .70 (175) .80 (200) .90 (225) 1.00 (250) 1.10 (275) 1.30 (325) 1.50 (375)
cfm
(L/s)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
BHP
RPM
(kW)
4200
(1980)
       
1.67
750
(1.25)
1.77
780
(1.32)
2.05
840
(1.53)
2.17
870
(1.62)
2.31
900
(1.72)
2.45
930
(1.83)
2.60
955
(2.07)
2.90
1010
(2.28)
3.14
1045
(2.34)
4400
(2075)
1.59
710
(1.19)
1.83
770
(1.41)
1.99
805
(1.48
2.24
860
(1.67)
2.39
890
(1.78)
2.51
915
(1.87)
2.67
945
(1.99)
2.83
970
(2.11)
3.12
1025
(2.33)
3.39
1060
(2.53)
4600
(2170)
1.78
735
(1.33)
2.13
795
(1.59)
2.17
825
(1.62)
2.45
880
(1.83)
2.60
910
(1.94)
2.75
935
(2.05)
2.89
960
(2.16)
3.06
990
(2.39)
3.38
1040
(2.66)
3.62
1075
(2.70)
4800
(2265)
2.00
760
(1.49)
2.27
820
(1.69)
2.43
850
(1.81)
2.70
905
(2.01)
2.85
930
(2.13)
3.01
955
(2.25)
3.26
980
(2.43)
3.33
1010
(2.48)
3.63
1055
(2.71)
3.87
1090
(2.89)
5000
(2360)
2.26
790
(1.69)
2.53
845
(1.89)
2.68
875
(2.00)
2.96
925
(2.21)
3.11
950
(2.32)
3.27
975
(2.44)
3.41
1000
(2.54)
3.58
1025
(2.67)
3.94
1075
(2.94)
4.16
1110
(3.10)
5200
(2455)
2.50
815
(1.87)
2.80
870
(2.09)
2.95
900
(2.20)
3.25
950
(2.42)
3.42
975
(2.55)
3.56
1000
(2.66)
3.75
1025
(2.80)
3.88
1045
(2.89)
4.23
1095
(3.16)
4.46
1125
(3.33)
5400
(2550)
2.79
840
(2.08)
3.07
895
(2.29)
3.24
920
(2.42)
3.55
970
(2.65)
3.70
995
(2.76)
3.87
1020
(2.89)
4.09
1045
(3.05)
4.22
1070
(3.15)
4.53
1110
(3.38)
4.81
1145
(3.59)
5600
(2645)
3.08
865
(2.30)
3.39
920
(2.53)
3.58
950
(2.67)
3.88
995
(2.89)
4.05
1020
(3.02)
4.22
1045
(3.15)
4.37
1065
(3.26)
4.57
1090
(3.41)
4.89
1130
(3.65)
5.16
1165
(3.85)
5800
(2735)
3.38
895
(2.52)
3.73
945
(2.78)
3.90
980
(2.91)
4.25
1020
(3.17)
4.42
1045
(3.30)
4.57
1065
(3.41)
4.76
1090
(3.55)
4.93
1110
(3.68)
5.25
1150
(3.92)
5.59
1185
(4.17)
NOTE  All data is measured external to the unit with dry coil and with the air filters in place. See Page 5 for Accessory Air Resistance data.
NOTE  Data in shaded area requires field furnished motor and drive.
NOTE  In Canada, maximum usable motor output is 3 hp (2.24 kW).