Submittal Sheet

QuickSetter
+
™ Low-lead
balancing valve with flow meter, press
connections
CALEFFI
Technical Data
Materials
Valve
Body: DZR low-lead brass
Ball: stainless steel
Ball control stem: brass, chrome plated
Ball seal seat: PTFE
Control stem guide: PSU
Seals: EPDM
Flow meter
Body and headwork: DZR low-lead brass
Bypass valve stem: stainless steel
Springs: stainless steel
Seals: peroxide-cured EPDM
Flow meter float and indicator cover: PSU
NSF/ANSI 372-2011, Drinking Water System Components-Lead Content
Reduction of Lead in Drinking Water Act, California Health and Safety Code
116875 S.3874, Reduction in Drinking Water Act, certified by ICC-ES, file PMG-
1360.
Performance
Suitable Fluids: water, glycol solutions
Max. percentage of glycol: 50%
Max. working pressure: 150 psi (10 bar)
Working temperature range: 14 - 230°F (-10–110°C)
Flow rate range unit of measurement: ½- 1 ¾ gpm; 2 - 7 gpm
Accuracy: ±10%
Control stem angle of rotation: 90°
Control stem adjustment wrench: 9 mm
Press connections: ¾ inch
Application
The QuickSetter+™ manual balancing valve contains a built-in flow
meter and sight gauge, negating the need for differential pressure
gauges and reference charts. Circuit balancing is fast, easy and
accurate. Constructed of low-lead brass, QuickSetter+™ is ideally
suited for use in plumbing applications such as hot water recirculation
systems. The built-in check valve protects against circuit thermo-
siphoning. The outlet temperature gauge (optional) verifies the fluid
temperature in the circuit. The flow meter sight gauge is dry (not
exposed to the fluid) thus eliminating the possibility of gauge clouding/
scaling over time.
Submittal Data 02936.1 NA — Issue Date 08/2017
Dimensions
*with temperature gauge.
Typical Specification
Furnish and install on the plans and described herein, a Caleffi QuickSetter+
balancing valve with flow meter as manufactured by Caleffi. Each balancing
valve must be designed with DZR low-lead brass body (<0.25% Lead
content) certified by ICC-ES, stainless steel ball, chrome-plated brass ball
control stem, PTFE ball seal seat, PSU control stem guide, DZR low-lead
brass flow meter body and headwork, stainless steel flow meter bypass valve
stem, stainless steel flow meter springs, PSU flow meter float and indicator
cover, peroxide-cured EPDM seals, and provided complete with inlet flow
check valve. Can be provided with optional mixed outlet termperature
gauge, 30 to 210°F scale, 2 inch diameter. Each balancing valve shall be a
Caleffi model 132 or approved equal. (See product instructions for specific
installation information.)
.
Job name ______________________________________
Job location ______________________________________
Engineer ______________________________________
Mechanical contractor ________________________________
Contractor’s P.O. No. ________________________________
Representative ________________________________
Size ________________________________________
Quantity ________________________________________
Approval ________________________________________
Service ________________________________________
Tag No. ________________________________________
Notes ________________________________________
D
C
B
MIX
30
50
70
90
110
130
150
170
190
210
˚F
D
A
0.50
0.50
1.00
0.75
0.75
1.00
1.25
1.25
1.50
1.75
P.
MAX 150 psi
T.
MAX 230˚F
GPM
1.50
1.75
Code A B C D
Wt
(lb)
132536AFC 3/4" 3 5/16" 1 13/16" 9 7/8" 1.8
132556AFC 3/4" 3 5/16" 1 13/16" 9 7/8" 1.8
Code A B C D
Wt
(lb)
132537AFC* 3/4" 3 5/16" 1 13/16" 12 1/8" 2.2
132557AFC* 3/4" 3 5/16" 1 13/16" 12 1/8" 2.2
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system.
© Copyright 2017 Caleffi

Summary of content (1 pages)