Install Instructions

Function
The QuickSetter+™ balancing valve accurately controls the flow rate
in plumbing systems. Proper system balancing ensures the system
operates according to design specifications, achieving, with the
QuickSetter+™, precise quick manually balanced hot water circuits.
The flow meter is housed in a bypass circuit on the valve body and can
be shut off during normal operation. The flow meter permits fast and easy
circuit balancing without added differential pressure gauges and charts.
Product range
132 Series Balancing valve with flow meter sizes 1/2”, 3/4”,
and 1”. Includes check valve and optional outlet
temperature gauge.
Technical characteristics
Valve
Material: Body and ball: low-lead brass (<0.25% lead content)
Ball control stem: 303 stainless steel
Ball seal seat: PTFE
Control stem guide: PSU
Seals: EPDM
Flow meter
Material: Body and headwork: low-lead brass (<0.25% lead content)
Valve stem: chrome plated brass
Springs: stainless steel
Seals: EPDM
Flow meter float and indicator cover: PSU
Performance: Max. working pressure: 150 psi (10 bar)
Max. glycol percentage: 50%
Working temperature range: 14–230°F (-10–110°C)
Flow rate range unit of measurement: gpm
Accuracy: ±10%
Control stem angle of rotation: 90°
Required operating wrench: 1/2”–1”: 9 mm
Connections: 1/2”, 3/4”, 1” union sweat
Reduction of Lead in Drinking Water Act Compliant: 0.25% Max.
weighted average lead content. Reduction of Lead in Drinking
Water Act Certified by IAPMO R&T
QuickSetter™ Balancing Valve with flow meter
132 Series
NA18070
www.caleffi.com
© Copyright 2014 Caleffi

Summary of content (8 pages)