Install Instructions
www.caleffi.com
1
© Copyright 2013 Caleffi
Function
The ThermoMix™ boiler protection high-flow thermostatic mixing valve
is used in hydronic heating systems with non-condensing boilers,
including solid fuel, biomass, gas, LP or oil-fired. It can be installed
with steel, cast iron and copper tube style boilers, automatically
controlling the return water temperature, preventing condensation of
the water vapor contained in the flue gas.
The 280 series ThermoMix valve mixes bypass flow from the boiler
with return flow from the system, sending a fixed temperature flow
to the boiler which protects against corrosion from condensation
occurring when a minimum flue gas temperature is not otherwise
maintained.
Changeable thermostatic sensor cartridges modifies the valve
temperature setting. The thermostatic sensor cartridge can easily be
removed for maintenance or to change the valve set temperature, with
out removing the valve body from the piping.
Product range
280 series boiler protection valve. NPT male or sweat union, sizes
1”, 1-1/4”.
Technical Characteristics
· Materials: - Body: brass
- Lower body plug: brass
- Shutter: polysulfone
- Spring: stainless steel
- Seal: EPDM
- Union seals: non-asbestos fiber
- Thermostatic sensor: wax
· Suitable fluids: water, glycol solutions
· Max. percentage of glycol: 50%
· Max. working pressure: 150 psi (10 bar)
· Working temperature range: 40–212°F (5–100°C)
· Thermostatic element setpoint: 130°F (55°C) standard
115°F(45°C), 140°F(60°C),
160°F(70°C) optional cartridges (field replaceable)
· Sensor cartridge accuracy: ±3.6°F (±2°C)
· By-pass from boiler complete closing
temperature: Tset + 18°F (+ 10°C)
· Cv: size 1”...10 Cv
size 1 1/4”.. 14 Cv
· Connections: - NPT male union: 1” and 1 1/4”
- sweat union: 1” and 1 1/4”
ThermoMix™ boiler protection high-flow thermostatic mixing valve
280 Series
NA10292.01
Installation, commissioning and servicing instructions