Product Overview

CALEFFI
ISO 9001 No. 0003
ACCREDITED
ISO 9001 FM 21654
AngleMix™
Angle-style thermostatic mixing valve
520 series
01266/18 NA
Function
The Caleffi AngleMix
520 series thermostatic mixing valve is used in
systems producing domestic hot water and easily mounts to the top of
water heaters. The mixed temperature outlet is inline with the hot water
inlet, facilitating trouble-free connection and reducing space required
for installation. The AngleMix maintains the desired output temperature
of the mixed water supplied at a constant set value compensating for
both temperature and pressure fluctuations of the incoming hot and
cold water. The mixing valve also features a thermal shut-off function
that operates in the event of a cold water supply failure at the inlet.
Also available as body only, for a wide variety of separately-ordered end
connections, the angle style body design offers improved fluid dynamics
for better performance and reduces installation labor and materials,
eliminating a piping elbow in typical installations.
The valve has been specifically certified to ASSE 1017 and Low Lead
Plumbing Law by ICC-ES.
Product range
5205__A series Adjustable three-way thermostatic mixing valve with mixed outlet temperature gauge and angle body
.....................................................................................................................................................connections ¾" sweat and press union
5205__AC series Adjustable three-way thermostatic mixing valve with mixed outlet temperature gauge, angle body with inlet port check valves
.....................................................................................................................................................connections ¾" sweat and press union
520051A: Adjustable three-way thermostatic mixing valve, angle style body only for field installed connection fittings and temperature gauge,
order separately...............................................................................................................................................connections 1” male union
Technical specications
Materials
- Valve body: DZR low-lead brass
- Shutter, seats and slide guides: PSU
- Springs: stainless steel
- Seals: peroxide-cured EPDM
- Adjustment knob ABS
Performance
Suitable fluids: water
Setting range: 95150° F (35–65° C)
Tolerance: ±3° F (±2° C)
Max. working pressure (static): 150 psi (10 bar)
Max. working pressure (dynamic): 75 psi (5 bar)
Max. hot water inlet temperature: 195° F (90° C)
Max. inlet pressure ratio (H/C or C/H) for optimal performance: 2:1
Minimum temperature difference between
hot water inlet and mixed water outlet
for optimal performance: 18° F (10° C)
Minimum flow to ensure optimal performance: 0.5 gpm (2 L/min)
Mixed outlet temperature gauge: 2" diameter
Scale from 30° F to 210° F
Certifications
1. ASSE 1017/CSA B125.3, certified by ICC-ES, file
PMG-1357.
2. NSF/ANSI 372-2011, Drinking Water System Components-
Lead Content Reduction of Lead in Drinking Water Act,
California Health and Safety Code 116875 S.3874,
Reduction of Lead in Drinking Water Act, certified by
ICC-ES, file PMG-1360.
Connections
- sweat union: ¾"
- press union: ¾"