Submittal Sheet

Submittal Data 02916 NA - Issue Date 04/2010
5213 Series
CA L E FF I
A
A
F
E
D
B B
C
A
A
A
F
E
D
B B
C
A
Dimensions
Code A B C D E F Weight (lb) (kg)
521342A 1/2
NPT
" 2 13/16" 5 11/16" 4 15/16" 3" 1 15/16" 1.50 0.68
521352A 3/4
NPT
" 2 13/16" 5 11/16" 4 15/16" 3" 1 15/16" 1.65 0.75
521362A 1
NPT
" 2 15/16" 5 7/8" 5 3/16" 3 1/4" 1 15/16" 1.85 0.84
521349A 1/2
SWT
" 2 11/16" 5 7/16" 4 5/8" 2 11/16" 1 15/16" 1.40 0.63
521359A 3/4
SWT
" 2 7/8" 5 3/4" 4 13/16" 2 15/16" 1 15/16" 1.55 0.70
521369A 1"
SWT
3 1/8" 5 5/16" 5 3/8" 3 1/4" 1 15/16" 1.74 0.79
Application
Three-way thermostatic mixing valves are used in applications
where the user must be protected from the danger of scalding
caused by hot water. The Caleffi 5213 series provides water at
a safe and usable temperature in situations where the control
of the temperature of the water discharging from a terminal
fitting is of the utmost importance, i.e. within hospitals,
schools, nursing homes, etc. The valve is designed to prevent
the flow of water discharging from the mixed water outlet in the
event of the failure of hot or cold supply. The Caleffi 5213
series is a high performance combination thermostatic and
pressure balanced mixing valve and has been specifically
ASSE 1070 listed (temperature can not exceed 120°F and
check valves are recommended). The valve is complete with
check valve at both hot and cold inlets.
Technical Data
Materials:
- Valve body and regulating spindle: low-lead brass
(<0.25 lead content)
- Internal shutter: PPO
- Sealing elements: EPDM
- Cover: ABS
Temperature adjustment range: 85-120°F (29-49°C)
Temperature set: must be commissioned on site
to achieve desired temperature
Temperature control: ±3°F (±2°C)
Minimum cold inlet temperature: 39°F (4°C)
Maximum cold inlet temperature: 85°F (29°C)
Minimum hot inlet temperature: 120°F (49°C)
Maximum hot inlet temperature: 185°F (85°C)
Maximum working pressure (static): 140 psi (10 bar)
Maximum working pressure (dynamic): 70 psi (5 bar)
Minimum working pressure (dynamic): 1.5 psi (0.1 bar)
Maximum unbalanced dynamic supply (hot/cold or cold/hot): 6:1
Minimum temperature dierential between hot water inlet and
mixed water outlet to ensure thermal shuto function: 18°F (10°C)
Minimum temperature dierential between mixed water outlet
and cold water inlet to ensure stable operation: 9°F (5°C)
Minimum ow rate for stable operation: 1 gpm (4 l/min)
Certied to: ASSE 1070 listed
Connections: 1/2” - 1” NPT male with union
1/2” - 1” sweat with union
Lead Plumbing Law Compliance: 0.25% Maximum weighted
average lead content
-Lead Plumbing Law Certied by IAPMO R&T
10
0.1
2
5
1
0.2
20
50
Δp (psi)
G (l/min) (
gpm
)
10
2
3
5
20
0.1
1
0.2
(psi) (bar)
10
2
3
5
20
1
0.5
10
2
5
20
0.01
0.1
0.02
1.0
0.2
0.3
0.5
4 4
0.4
0.3
Kv=1.7 (m
3
/h)Cv= 2
Typical Specification
Furnish and install on the plans described herein, a Caleffi
Three-way thermostatic Mixing Valve as manufactured by
Caleffi. Each mixing valve must be designed with a brass
body, a replaceable brass cartridge chemical nickel plated
integrated inlet port check valves, stainless steel springs and
seals in EPDM. Each valve must also be designed for ±3°F
(±2°C) temperature stability with a tamper proof control knob
to lock the temperature at the set value. The valve shall be
ASSE 1070 approved for point of use installation. Each
valve shall be Caleffi model 5213 of approved equal. (See
product instructions for specific installation information.)
Cale North America, Inc. 3883 West Milwaukee Road / Milwaukee, WI 53208
Tel: 414.238.2360 / Fax: 414.238.2366 / www.cale.us © Copyright 2010 Cale
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system.
Size ...................................................................................................
Quantity ............................................................................................
Approval ............................................................................................
Service ...............................................................................................
Tag No. ..............................................................................................
Notes .................................................................................................
Job name ..........................................................................................
Job location .......................................................................................
Engineer ............................................................................................
Mechanical contractor ........................................................................
Contractorʼs P.O. No. ..........................................................................
Representative ...................................................................................
ASSE 1070
Scald Protection Three-Way
Thermostatic Mixing Valve
NSF
.