Install Instructions
Function
The backflow preventer can be used in all systems where there is
danger of the potable water supply system being contaminated. It
prevents an accidental reduction in the pressure in the distribution
system from causing backflow from contaminated water in user
installations.
The valve is ICC-ES certified to ASSE 1013, CSA B64.4 and NSF
372 low lead laws. It meets codes IPC, IRC and UPC for use in
accordance with the US and Canadian plumbing codes.
Product range
574 series testable, reduced pressure zone backflow preventer
574 Series
© Copyright 2018 Caleffi
H0003953.01
www.caleffi.com
Technical specifications
Materials
Body: DZR low-lead brass, EN 1982 CB752S
Cover: DZR low-lead brass, EN 12165 CW724R
Check valves: PSU-POM
Springs: stainless steel
Diaphragms and seals: peroxide-cured EPDM
Isolation ball valves, inlet and outlet
Body material: C89833 bronze
Ball: 304 stainless steel
Handle and nut: steel
Seat ring and packing gland: PTFE
Gland nut: brass
Stem: low lead brass
Performance
Suitable Fluids: water
Max. working pressure: 150 psi (10 bar)
Max. working temperature: 150°F (65°C)
Pressure test ports: upstream, intermediate, downstream
Connections: ½” NPT female & press
¾” NPT female & press
Certifications
1. ICC-ES certified to ASSE 1013, CSA B64.4 and NSF 372.
2. NSF/ANSI 372-2011, Drinking Water System Components-Lead Content Reduction of Lead
in Drinking Water Act, California Health and Safety Code 116875 S.3874, Reduction in
Drinking Water Act,certified by ICC-ES, file PMG-1360.
ASSE 1013
1
574 series Testable reduced pressure zone backflow preventer
code 574004A...................................................size ½" NPT female
code 574064A............................................................size ½" press
code 574050A...................................................size ¾" NPT female
code 574056A............................................................size ¾" press