Install Instructions

Function
The balancing valve accurately controls the flow rate of heating and
cooling transfer fluid supplied to fan coils and terminal units; or where
flow balancing is required in solar thermal systems. Proper hydronic
system balancing ensures the system operates according to design
specifications, providing satisfactory thermal comfort with low energy
consumption.
The flow meter is housed in a by-pass circuit on the valve body and
can be shut off during normal operation. The flow meter permits
fast and easy circuit balancing without added differential pressure
gages and charts. The balancing valve comes standard with a hot
pre-formed insulation shell to optimize thermal performance for both
hot and chilled water.
These items are designed for use in closed hydronic systems. Do
not use in plumbing applications. These items do not meet the low-
lead plumbing standards of U.S. and Canada.
QuickSetter™ Balancing Valve with Flow Meter
132 Series
© Copyright 2020 Caleffi
18106.06
www.caleffi.com
1
Product range
132 Series Balancing valve with flow meter sizes 1/2", 3/4", 1", 1-1/4",
1-1/2", 2" NPT female and press
Technical specications
Valve: Body and ball: brass
Ball control stem: chrome-plated brass
Ball seal seat: PTFE
Control stem guide: PSU
Seals: peroxide-cured EPDM
Flow meter: Body: brass
Bypass valve stem: chrome-plated brass
Springs: stainless steel
Seals: peroxide-cured EPDM
Flow meter float and indicator cover: PSU
Performance: Max. percentage of glycol: 50%
Max. working pres sure: 150 psi (10 bar)
Working temperature range: 14 - 230°F (-10–110°C)
Flow rate range unit of measurement: gpm
Accuracy: ±10%
Control stem angle of rotation: 90°
Required operating wrench: 1/2”–1 1/4”: 9 mm
1 1/2” and 2”: 12 mm
Connections : 1/2”– 2” FNPT; 1/2" – 2” press
Flow rate correction factor: 20% - 30% glycol solutions: 0.9
40% - 50% glycol solutions: 0.8
Insulation shell: closed cell expanded PE-X, 10 mm thick
(see page 7 for specification)