Brochure

Draining off dirt
The dirt separator collection chamber
is fitted with a ball drain cock. Using
the handle provided it is possible to
drain off impurities even with the
system in operation.
Use of top connector
The connector on top of the dirt separator can be used for optional
installation of an automatic air vent
valve, Caleffi code 502243A for the
threaded or sweat versions- 5462
Series (A), replacing the standard
1/2" NPT Male plug (pn NA10044).
Use Caleffi code 501502A for the
flanged version 5465 Series (B) -
replacing the
standard 3/4" NPT
End Cap (pn 41525).
Use bottom connector
The dirt separators come complete with drain cocks installed on
the bottom port: Caleffi code 538402 FD for
threaded or sweat
versions- 5462 Series (A), code 39753 for the flanged version - 5465
Series (B).
Tmax 110C
P
max 10 bar
Tmax 105C
P
max 10 bar
BI-DIRECTIONAL
A
B
Maintenance
To perform maintenance, simply use
a 26 mm hexagon wrench (1) to
unscrew the dirt collection chamber,
to which the inner element is fixed in
such a way that it can be removed
for cleaning.
1
Geometric structure and large dirt collection chamber
The geometrical structure of DIRTCAL means that, inside it, the flow
speed is slowed down to help separate the particles of impurities.
The dirt collection chamber has the following features:
- It is located at the bottom of the device at such a distance from
the connections that the collected impurities are not affected by
the swirl of the flow through the screen.
- It has enough capacity to increase the amount of sludge stored
and therefore decrease the frequency of emptying/discharging it
in contrast to filters that need to be frequently cleaned.
- It is easy to inspect, by unscrewing the lower half from the valve
body for servicing the internal element to remove fiber or large
impurities.