Install Instructions

www.caleffi.com N A 1 0 0 7 3 .03
Z-one Z1, Z2, Z3 Series
Function
The Z-one, a two-position spring return zone valve,
is used in heating and air-conditioning systems.
The Z-one series consist of a Z1 actuator which is
easily attached to a Z2 (2-way) or Z3 (3-way) valve
body. Z1 actuator is equipped with or without
auxiliary switch.
The Z-one actuator has a synchronous motor that
winds the return spring and moves the valve paddle
to the desired position. When power is removed the
actuator spring returns the valve paddle. 24V
actuators use a sealed reed switch for end switch,
requiring no minimum current load.
US Patent 7,048,251
Technical Characteristics of Body
Material: - body: forged brass
(optional lead-free brass, see page 4 for cert statement)
- seat: machined brass
- stem: stainless steel
- two o-ring seals EPDM
- paddle EPDM
Medium: water and glycol
Maximum percent of glycol: 50%
Temperature range: 32 to 240°F (0 115°C)
Max. static pressure: 15 psi (1 bar) steam
300 psi (20 bar)
Connection: -press (lay length: 3-3/4; overall length 5-5/8) ¾”
-sweat ½”, ¾” 1” & 1 ¼”
- NPT ½”, ¾” & 1”
- SAE flare ½”
- inverted flare ½”, ¾” & 1” sweat fittings separate
Technical Characteristics of Actuator
Material: - base and cover: polycarbonate
- base plate: aluminum
Motor: - voltage: 24 VAC 50/60 Hz Class 2
120 VAC 50/60 Hz
208 VAC 50/60 Hz
230 VAC 50/60 Hz
277 VAC 50/60 Hz
Wire lead length: 6 (15cm), 24V only -18 (45cm)
Power requirements: 5.0 W, 7 VA
Ambient temperature range: 32 - 104ºF (170ºF optional)
Auxiliary switch: 24 VAC: 0.0 A min,
0.4 A max, 24 V
120-277 VAC:
0.25A min, 5A max, 250 V
Humidity: 95% non-condensing
Approvals: UL873, cUL Listed & CE
UL 1995 sec. 18 (air plenum & ducts)
Normally Open Actuators must be powered down during off-season.

Summary of content (8 pages)