User guide
18 HYDRA2 Operator Manual
Introduction - Hydra2 Networking
I/O BOX IDENTIFICATION
Each I/O box on the Hydra2 network 
needs to be given a unique ID in the 
form of a number between 0 and 255. 
The Hydra ID, or “HID” for each box 
is set using a DIP switch accessible 
from the rear of fixed format I/O 
boxes, or on the side of the controller 
card within a modular I/O box. 
Label pockets are fitted to the front panel 
of I/O boxes to aid visual identification.
Fixed Format I/O boxes
The 8 way DIP switch is set as an 8 bit 
binary representation of the HID value 
with the left hand switch used for the 
most significant bit, and the right hand 
switch for the least significant bit. A switch 
in the down / off position represents 
a binary 0 and a switch set in the up / 
on position represents a binary 1. Each 
switch / binary bit equates to a decimal 
value, starting at 1 for the least significant 
bit. The remaining switches are double 
the value of their less significant neighbor, 
making the 8th / most significant bit 
equate to a decimal value of 128.
All fixed format I/O box ID switches are 
orientated the same way, though some 
boxes, such as MADI units, use a different 
style switch with more pronounced 
labelling. Ignore any labels on the switch 
itself and always refer to the Calrec  
labelling on the surrounding panel which 
will show the most significant bit switch on 
the left and the binary 1 position as up.
Care should be taken when setting HIDs 
to avoid accidentally duplicating the same 
ID on more than one box. Duplicate box 
IDs can cause network conflicts. I/O 
boxes should be disconnected from the 
network before changing their HID, and 
reset or power cycled once the DIP switch 
is set to ensure the new HID is active 
before reconnecting to the network.
If replacing an I/O box for any reason, 
choosing a box of the same type as the 
original and setting it with the same ID 
makes it a drop-in replacement which will 
work with existing user memories and 
settings, requiring no further configuration.
When connecting additional I/O boxes to 
a network it is important to be aware of 
the existing I/O HIDs in order to select 
a unique number and avoid creating a 
conflict.
Address 2
Some I/O boxes, such as MADI units, 
are fitted with 2 banks of DIP switches—
Address 1 and Address 2—to provide 
a 16 bit ID, and therefore a greater 
range of values. Please note that only ID 
values between 0 and 255 are currently 
supported. Any DIP switches labelled 
Address 2 should all be set to the off 
position.
Modular I/O box ID setting
The ID for modular I/O boxes is set by 
a DIP switch on the controller card and 
is only accessible by removing the card. 
Please refer to the Hydra2 installation 
manual and ensure ESD precautions are 
observed before removing any modular 
I/O box cards.
ID switches on modular I/O controller 
cards are orientated differently. Ignore any 
labelling on the switch itself and refer to 
the Calrec labelling printed on the circuit 
board around the switch to clarify its 
orientation. When viewing the card from 
the side, the most significant bit is on the 
left and the least significant bit on the 
right. Pulling a switch towards you sets it 
as a binary 1, away from you as a binary 
0. The following illustrations show the 
ID switch on the modular I/O controller 
card from the side and top views. Again 
the decimal value of 39 is used for the 
example.
1
1 0234567
ADDRESS
0
1
0
0 0 1 0 0 1 1 1
128 64 32 16 8 4 2 1
32 4 2 1 =+++ 39
STANDARD SWITCH FOR HID SETTING
•  The above diagram shows how 
each switch relates to a decimal 
value. The setting shown in the 
example provides a decimal 
HID value of 39
MODULAR I/O CONTROLLER - SIDE 
01234567
ID BITS
Sw3
1248163264128
Front Panel
1 2 4 8 16 32 64 128
MODULAR I/O - VIEWED FROM TOP 
Front Panel










