INSTRUCTION MANUAL 10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers Revision: 3/14 C o p y r i g h t © 1 9 9 8 - 2 0 1 4 C a m p b e l l S c i e n t i f i c , I n c .
Limited Warranty “Products manufactured by CSI are warranted by CSI to be free from defects in materials and workmanship under normal use and service for twelve months from the date of shipment unless otherwise specified in the corresponding product manual. (Product manuals are available for review online at www.campbellsci.com.) Products not manufactured by CSI, but that are resold by CSI, are warranted only to the limits extended by the original manufacturer.
Assistance Products may not be returned without prior authorization. The following contact information is for US and international customers residing in countries served by Campbell Scientific, Inc. directly. Affiliate companies handle repairs for customers within their territories. Please visit www.campbellsci.com to determine which Campbell Scientific company serves your country. To obtain a Returned Materials Authorization (RMA), contact CAMPBELL SCIENTIFIC, INC., phone (435) 227-9000.
Table of Contents PDF viewers: These page numbers refer to the printed version of this document. Use the PDF reader bookmarks tab for links to specific sections. 1. General ........................................................................ 1 2. Specifications ............................................................. 1 2.1 Cable Length Considerations ............................................................... 1 3. Wiring .......................................................................
Table of Contents ii
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 1. General The 10164-L sampler control cable enables a datalogger to trigger an Isco, American Sigma, or connector-compatible autosampler. Through this cable, the datalogger can inhibit the sampler from running its programmed sampling routine and sense and record when the sampler indicates that it has taken a sample. Each of these functions is independent of the others and may be combined as desired. 2.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 3. Wiring 3.1 General Wiring Information FIGURE 3-1 shows a schematic of the 10164 and TABLE 3-1 shows pin connector and wire functions. Sections 3.2 through 3.4 provide information about connecting the wires to a datalogger. The datalogger wiring depends on the function. FIGURE 3-1. 10164 Sampler Control Cable Schematic TABLE 3-1.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 3.2 Triggering Sampler TABLE 3-2 shows the datalogger connections required to trigger the sampler. TABLE 3-2. Datalogger Wiring for Triggering Sampler NOTE 3.3 CR800 CR850 CR1000 CR3000 CR500 CR510 CR10(X) CR23X 21X Color Description Purple Ground Yellow Control Port Control Port (C1, C2,…) Control Port (C1, C2,…) Control Red Power 12V 12V +12 Clear Shield G G Insulate and tuck the unused wires out of the way.
164-L Sampler Control Cable for use with Isco and Sigma Autosamplers TABLE 3-4. Datalogger Wiring to Inhibit a Sigma Sampler Program Color Description Purple Ground Brown Control Port Clear Shield CR800 CR850 CR1000 CR3000 CR500 CR510 CR10(X) CR23X 21X G Control Port (C1, C2,…) Control Port (C1, C2,…) Control G TABLE 3-5. Datalogger Wiring to Inhibit an Isco Sampler Program NOTE 4.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 4.1 CRBasic Programming 4.1.1 Trigger Sampler To trigger the sampler, the datalogger program must set the port high, delay for at least 0.5 seconds, and then set the port low. TABLE 4-1.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 'CR1000 Series Datalogger 'Declare Public Variables Public Events 'Define Data Tables DataTable (Sampler,1,1000) Totalize (1,Events,FP2,False) EndTable 'Main Program BeginProg Scan (1,Sec,0,0) PulseCount (Events,1,1,0,0,1.0,0) 'Call Output Tables CallTable Sampler NextScan EndProg 4.1.3 Inhibit Sampler’s Program To inhibit a sampler’s onboard program, use the PortSet() instruction.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers TABLE 4-4. Wiring for Example of Inhibiting a Sigma Sampler Onboard Program Color Description Purple Ground Brown Control Port Clear Shield CR800, CR850, CR1000, or CR3000 C1 For samplers such as the products manufactured by Sigma, the onboard program is inhibited by setting the control port high.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers You can also supply the trigger signal from switched excitation if no control ports are available. In this case, connect the yellow cable to the desired excitation channel (say E3) and pulse the channel using Instruction 22 as follows: Excitation with Delay (P22) 1: 3 EX Chan (or the channel you select) 2: 50 Delay w/EX (units=0.01sec) 3: 0 Delay after EX (units=0.01sec) 4: 2500 mV Excitation 4.2.2 Sense Sampler Event Markers 4.2.2.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 3: Do (P86) 1: 10 Set high Flag 0 (output flag) 4: Set Active Storage Area (P80) 1: 1 Final Storage Area 1 2: 400 Array ID or location 5: Real Time 1: 1110 (P77) Year,Day,Hour-Minute 6: Sample (P70) 1: 1 Reps 2: 10 Loc [ Sample_No ] 7: End (P95) ;of Subroutine Number 98 End Table 3 4.2.
10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers 10
Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES www.campbellsci.com • info@campbellsci.com Campbell Scientific Centro Caribe S.A. (CSCC) 300 N Cementerio, Edificio Breller Santo Domingo, Heredia 40305 COSTA RICA www.campbellsci.cc • info@campbellsci.cc Campbell Scientific Africa Pty. Ltd. (CSAf) PO Box 2450 Somerset West 7129 SOUTH AFRICA www.csafrica.co.za • cleroux@csafrica.co.za Campbell Scientific Ltd.