User guide
CS210 Enclosure Humidity Sensor 
'Define Data Tables 
DataTable (Daily,1,-1) 
 DataInterval (0,1,Day,10) 
 Minimum (1,Batt_Volt,FP2,0,False) 
 Minimum (1,PanelTempC,FP2,False,False) 
 Maximum (1,PanelTempC,FP2,False,False) 
 Maximum (1,Enc_RH,FP2,False,False)   
EndTable 
'Main Program 
BeginProg 
 Scan (10,Sec,0,0) 
 PanelTemp (PanelTempC,250) 
 Battery (Batt_volt) 
    'Measure CS210. Sensor is on all the time. Don't need a delay. 
 VoltSe (Enc_RH,1,mV2500,1,1,0,250,0.1,0) 
    'Set the sensor to 100% if it exceeds 100%. 
    If Enc_RH > 100 Then Enc_RH = 100 
 CallTable Daily 
 NextScan 
EndProg 
Example 2. Sample CR200 Program 
'CR200 Series Datalogger 
'To create a different opening program template, type in new 
'instructions and select Template | Save as Default Template 
'date: 
'program author: 
'SENSOR WIRING 
'CS210 
'Black: C2 
'White: SE1 
'Clear: G 
'Declare Public Variables 
'Example: 
Public batt_volt 
Public Enc_RH 
'Define Data Tables 
DataTable (Daily,1,-1) 
 DataInterval (0,24,hr) 
 Minimum (1,batt_volt,0,0) 
 Maximum (1,Enc_RH,False,0) 
EndTable 
4 