CS475, CS476, and CS477 Radar Water Level Sensor 
TABLE 4-5. Example of a Start False Echo Learn Command 
Initial Command  Response 
0XSFEL+2.500! 
Where (from left to right), 
0—sensor’s address; 
2.500—the water surface distance. 
02001<cr><If> 
Where (from left to right), 
0—sensor’s address; 
200—the amount of time (in seconds) 
that you must wait before sending the 
send data command; 
1—the number of values that will be 
placed in the buffer. 
Subsequent Command  Response 
0D0! 
Where the first zero is the sensor 
address. 
This is the send data command. 
0+2.500<cr><lf> 
Where (from left to right), 
0—sensor’s address; 
2.500—the water surface distance. 
4.3  Step 3 — Do a Set Water Stage Command 
The 25616, Adjustment/Display Module, or the terminal emulator 
in LoggerNet or PC400 can be used to enter SDI-12 commands.  
Appendix  B.2,  Using  Terminal Emulator and a Datalogger to 
Send Commands,  describes entering commands using the 
terminal emulator. 
NOTE 
Do a Set Water Stage command followed by a Send Data command (see 
TABLE 4-6). To set the water stage, do an aXSS+nnn.nnn! command (where 
nnn.nnn = the initial water depth) followed by the aD0! (Send Data) command. 
TABLE 4-6 shows an example of the command and response for entering this 
setting. 
Appendix B describes this command in further detail. 
TABLE 4-6. Example for Setting Water Stage 
Initial Command  Response 
0XSS+7.010! 
Where (from left to right), 
0—sensor’s address; 
7.010—the initial water depth value 
used to calculate subsequent stage 
measurements. 
00011<cr><If> 
Where (from left to right), 
0—sensor’s address; 
001—the amount of time (in seconds) 
that you must wait before sending the 
send data command; 
1—the number of values that will be 
placed in the buffer. 